29
Indoor Unit MCAV127R5VAB
Outdoor Unit GR129R5TBA
COOLING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230V 1-phase 50Hz
Rating Conditions Running Amps. A 0.13 0.28 5.39 5.8
Power Input kW 0.031 0.062 1.177 1.27
Full Load Conditions Running Amps. A 0.13 0.28 6.79 7.2
Power Input kW 0.031 0.062 1.507 1.60
Rating Conditions : Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
HEATING
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230V 1-phase 50Hz
Rating Conditions Running Amps. A 0.13 0.28 5.99 6.4
Power Input kW 0.031 0.062 1.327 1.42
Full Load Conditions Running Amps. A 0.13 0.28 7.09 7.5
Power Input kW 0.031 0.062 1.557 1.650
Rating Conditions : Indoor Air Temperature 20°C D.B.
Outdoor Air Temperature 7°C D.B. / 6°C W.B.
Full Load Conditions : Indoor Air Temperature 27°C D.B.
Outdoor Air Temperature 24°C D.B. / 18°C W.B.