1. Specifications
1
1
2
3
4
5
I - 74
TC
: Total Cooling Capacity
(kW)
SHC : Sensible Heat Capacity
(kW)
CI
: Compressor Input
(kW)
Rating conditions are
: Outdoor Ambient Temp. 35
°
C DB
: Indoor Unit Entering Air Temp. 27
°
C DB / 19
°
C WB
RATING CAPACITY :
7.3 kW
AIR FLOW RATE :
1140 CMH
EVAPORATOR
CONDENSER
ENT. TEMP.
°
C
AMBIENT TEMP
°
C
WB
DB
25
30
35
40
45
TC
7.37
7.03
6.67
6.26
5.81
CI
2.07
2.22
2.38
2.49
2.62
21
SHC
4.66
4.47
4.28
4.06
3.83
15
23
SHC
5.21
5.03
4.83
4.61
4.39
25
SHC
5.77
5.58
5.39
5.17
4.94
27
SHC
6.33
6.14
5.95
5.73
5.5
29
SHC
6.88
6.7
6.51
6.26
5.81
31
SHC
7.37
7.03
6.67
6.26
5.81
TC
7.61
7.31
6.96
6.59
6.18
CI
2.13
2.28
2.44
2.57
2.69
21
SHC
3.93
3.78
3.6
3.42
3.23
17
23
SHC
4.49
4.34
4.16
3.98
3.78
25
SHC
5.05
4.89
4.72
4.54
4.34
27
SHC
5.6
5.45
5.28
5.09
4.9
29
SHC
6.16
6.01
5.83
5.65
5.46
31
SHC
6.72
6.56
6.39
6.21
6.01
TC
7.88
7.6
# 7.3
6.94
6.54
CI
2.19
2.35
2.52
2.65
2.77
21
SHC
3.21
3.08
2.94
2.77
2.6
19
23
SHC
3.76
3.63
3.49
3.33
3.16
25
SHC
4.32
4.19
4.05
3.89
3.71
27
SHC
4.88
4.75
4.61
4.45
4.27
29
SHC
5.44
5.31
5.17
5
4.83
31
SHC
5.99
5.86
5.72
5.56
5.39
TC
8.14
7.85
7.56
7.21
6.86
CI
2.25
2.41
2.59
2.72
2.85
23
SHC
3.03
2.91
2.78
2.64
2.5
21
25
SHC
3.59
3.47
3.34
3.2
3.05
27
SHC
4.15
4.03
3.9
3.75
3.61
29
SHC
4.7
4.58
4.46
4.31
4.17
31
SHC
5.26
5.14
5.01
4.87
4.73
TC
8.42
8.17
7.88
7.59
7.24
CI
2.31
2.48
2.66
2.79
2.93
23
25
SHC
2.86
2.76
2.65
2.54
2.41
27
SHC
3.42
3.32
3.21
3.1
2.97
29
SHC
3.97
3.88
3.77
3.65
3.52
31
SHC
4.53
4.44
4.32
4.21
4.08
TC
8.76
8.45
8.2
7.91
7.61
CI
2.39
2.56
2.71
2.87
3.02
25
27
SHC
2.71
2.6
2.51
2.41
2.3
29
SHC
3.27
3.15
3.06
2.97
2.86
31
SHC
3.82
3.71
3.62
3.52
3.42
1-7
Cooling Capacity
Indoor Unit : CAV250R5TAA Outdoor Unit : GRV250R7TAA
GRV250L7TAA