1. Specifications
1
1
2
3
4
5
I - 52
1-3
Other Component Specifications
4-Way Air Discharge Semi-concealed Type
MODEL NO.
Indoor Unit
CAV250 ~480R5TAA
Power Transformer
ATR-II215TA
Rated
Primary
VAC, Hz
230 V, 50 Hz
Secondary
10.2 V 1.4 A
14 V 0.5 A
Coil resistance
Ω
WHT – WHT : 84
,
BRN – BRN : 0.7
RED – RED : 2.7
Thermal cut off temperature
˚ C
145
Thermistor (Coil sensor) : TH2, 3, 4
PB3M-41E-S4 , PBC-41E-S25 , PBC-41E-S26 , PBC-41E-S36
Resistance
K
Ω
-10 ˚C : 23.7
±
5 %
,
20 ˚C : 6.5
±
5 %
-5 ˚C : 18.8
±
5 %
,
30 ˚C : 4.4
±
5 %
0 ˚C : 15.0
±
5 %
,
40 ˚C : 3.1
±
5 %
5 ˚C : 12.1
±
5 %
,
45 ˚C : 2.6
±
5 %
10 ˚C : 9.7
±
5 %
Thermistor (Room sensor) : TH1
KTEC-35-S6
Resistance
K
Ω
0 ˚C :16.5
±
5 %
,
40 ˚C : 2.7
±
5 %
5 ˚C :12.8
±
5 %
,
45 ˚C : 2.2
±
5 %
10 ˚C :10.0
±
5 %
,
50 ˚C : 1.8
±
5 %
20 ˚C : 6.3
±
5 %
,
55 ˚C : 1.5
±
5 %
30 ˚C : 4.0
±
5 %
Electronic expansion valve
Valve body
IKV-24D12 (CAV250R5TAA)
HKV-30D16 (CAV360-480R5TAA)
Coil
DKV-MOZS582E0 (CAV250R5TAA)
EKV-MOZS584E0 (CAV360-480R5TAA)
Drain pump
WP20SL-21
Rated
230 V, 14.7 W
Float switch
FS-0218-102 (CAV250R5TAA)
FS-0218-103 (CAV360-480R5TAA)
Rated (Contact rated)
DC 12 V, 25 W