1. Specifications
1
1
2
3
4
5
I - 108
1-11 Installation Instructions
Electrical Characteristics
Indoor Unit : CAV250R5TAA Outdoor Unit : GRV250R7TAA
GRV250L7TAA
Cooling:
Rating Conditions
:
Indoor Air Temperature
27
°
C DB / 19
°
C WB
Outdoor Air Temperature 35
°
C DB
Full Load Conditions
:
Indoor Air Temperature
35
°
C DB / 25
°
C WB
Outdoor Air Temperature 43
°
C DB
Heating:
Rating Conditions
:
Indoor Air Temperature
20
°
C DB
Outdoor Air Temperature
7
°
C DB / 6
°
C WB
Full Load Conditions
:
Indoor Air Temperature
27
°
C DB
Outdoor Air Temperature 21
°
C DB / 15.5
°
C WB
●
Cooling
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 3 phase / 50 Hz
Rating conditions
A
0.6 / 0.63
0.62 / 0.65
4.45 / 4.35
4.82 / 4.73
kW
130 / 150
0.13 / 0.15
2.5 / 2.52
2.76 / 2.82
Full load conditions
A
0.6 / 0.63
0.62 / 0.65
5.3 / 5.32
5.67 / 5.69
kW
130 / 150
0.13 / 0.15
2.98 / 3.02
3.24 / 3.32
Starting amperes
A
1 / 1
1 / 1
25 / 28
27 / 30
●
Heating (Heat pump only)
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
220 - 240 V / 1 phase / 50 Hz
380 - 415 V / 3 phase / 50 Hz
Rating conditions
A
0.37 / 0.42
0.62 / 0.65
5 / 4.8
5.31 / 5.12
kW
80 / 100
0.13 / 0.15
2.79 / 2.81
3 / 3.06
Full load conditions
A
0.37 / 0.42
0.62 / 0.65
5.1 / 4.9
5.41 / 5.22
kW
80 / 100
0.13 / 0.15
2.87 / 2.89
3.08 / 3.14
Starting amperes
A
1 / 1
1 / 1
25 / 28
27 / 30