1. Specifications
1
2
3
4
5
I - 81
1-7
Cooling Capacity
Indoor Unit : DSAV250R5TAA
Outdoor Unit : GRV250R5TAA
GRV250L5TAA
TC
: Total Cooling Capacity
(kW)
SHC : Sensible Heat Capacity
(kW)
CI
: Compressor Input
(kW)
Rating conditions are
: Outdoor Ambient Temp. 35
°
C DB
: Indoor Unit Entering Air Temp. 27
°
C DB / 19
°
C WB
RATING CAPACITY :
7.3 kW
AIR FLOW RATE :
1080 CMH
EVAPORATOR
CONDENSER
ENT. TEMP.
°
C
AMBIENT TEMP
°
C
WB
DB
25
30
35
40
45
TC
7.37
7.03
6.67
6.26
5.81
CI
2.35
2.51
2.69
2.63
2.58
21
SHC
4.86
4.68
4.5
4.28
4.06
15
23
SHC
5.44
5.26
5.07
4.86
4.64
25
SHC
6.02
5.84
5.65
5.44
5.22
27
SHC
6.59
6.41
6.23
6.02
5.8
29
SHC
7.17
6.99
6.67
6.26
5.81
31
SHC
7.37
7.03
6.67
6.26
5.81
TC
7.61
7.31
6.96
6.59
6.18
CI
2.41
2.58
2.76
2.71
2.65
21
SHC
4.13
3.99
3.82
3.64
3.46
17
23
SHC
4.71
4.56
4.4
4.22
4.03
25
SHC
5.29
5.14
4.97
4.8
4.61
27
SHC
5.87
5.72
5.55
5.38
5.19
29
SHC
6.44
6.3
6.13
5.95
5.76
31
SHC
7.02
6.87
6.71
6.53
6.18
TC
7.88
7.6
# 7.3
6.94
6.54
CI
2.48
2.66
2.85
2.8
2.75
21
SHC
3.41
3.28
3.15
2.99
2.82
19
23
SHC
3.98
3.86
3.72
3.57
3.4
25
SHC
4.56
4.44
4.3
4.14
3.97
27
SHC
5.14
5.01
4.88
4.72
4.55
29
SHC
5.72
5.59
5.46
5.3
5.13
31
SHC
6.29
6.17
6.03
5.88
5.71
TC
8.14
7.85
7.56
7.21
6.86
CI
2.55
2.73
2.93
2.89
2.84
23
SHC
3.25
3.13
3.01
2.87
2.73
21
25
SHC
3.82
3.71
3.59
3.45
3.31
27
SHC
4.4
4.29
4.16
4.02
3.88
29
SHC
4.98
4.86
4.74
4.6
4.46
31
SHC
5.56
5.44
5.32
5.18
5.04
TC
8.42
8.17
7.88
7.59
7.24
CI
2.62
2.8
3.01
2.97
2.93
23
25
SHC
3.09
3
2.89
2.78
2.66
27
SHC
3.67
3.58
3.47
3.36
3.23
29
SHC
4.25
4.15
4.04
3.94
3.81
31
SHC
4.82
4.73
4.62
4.51
4.39
TC
8.76
8.45
8.2
7.91
7.61
CI
2.7
2.89
3.07
3.05
3.03
25
27
SHC
2.95
2.85
2.76
2.67
2.56
29
SHC
3.53
3.42
3.34
3.24
3.14
31
SHC
4.11
4
3.91
3.82
3.72