Communication GUI Guide
GXE600 Series
TDK-Lambda
<Page>
36/41
#
Starting Address
Qty. Function
RC Setting
・
RC Mode
GXE has two remote control signals of analog RC input
and communication RC input.
Value
Overview
0
The analog RC input is used as
the remote control signal.
Communication RC input is not referred.
(Factory setting)
1
The volatile remote On / Off register is used
as the remote control signal.
Analog RC input is not referred.
2
The Nonvolatile remote On / Off register is used
as the remote control signal.
Analog RC input is not referred.
3
The logical AND of the analog RC and the volatile
remote On / Off register is used as the remote
control signal.
Output is turned On when both inputs are remote On.
Nonvolatile remote On / Off registers are
not referenced.
4
The logical AND of the analog RC and the
Nonvolatile remote On / Off register is used as
the remote control signal.
Output is turned On when both inputs are remote On.
Volatile remote On / Off registers are not referenced.
・
Filter sensitivity
Bounce (chattering) may occur due to the input signal from the
external terminal.
The GXE has a bounce removal function, and the bounce removal
intensity can be adjusted by setting the filter sensitivity.
T he register setting value
Max.
Min.
Factory settting
Unit
Integer data
100
0
10
ms
3
PVCC Setting
101
1
Register for setting the output reference value.
GXE has two output reference, which are PV / CC terminal reference
(Analog PV / CC) and PV / CC communication reference
(Digital PV / CC).
PV reference : T he output voltage reference is selected.
CC reference : T he output current reference value is selected.
T he register setting value
Function
Digital
Analog Factory settting
PV reference
1
0
0
CC reference
1
0
0
reserved
-
-
-
For example, when the external terminal input (Analog) is selected,
the set value of the communication register is not referenced.
2 - 15
Holding Register
Data form
(0x0065)
bit
0
1