<Page>
5. Connection method
Pay attention to the input wiring. If it is connected to wrong terminal, the power supply will be damaged.
•
Input must be off when making connections.
•
Connect terminal to earth (frame ground of the equipment etc.) by thick wire for safety and
improvement of noise sensitivity.
• Basic connection (Local sensing)
Connect "+S" terminal (Pin No.2) to "+Vm" terminal (Pin No.1), and "S" terminal (Pin No.6) to "Vm"
terminal (Pin No.5) with the attached short pieces. (Short pieces are mounted at time of shipment.)
Recommended torque : Input terminal
M3.5 screw
1.0Nꞏm
(
10.2kgfꞏcm
)
~ 1.6Nꞏm
(
16.3kgfꞏcm
)
Output terminal M4 screw
1.2Nꞏm
(
12.0kgfꞏcm
)
~ 1.6Nꞏm
(
16.3kgfꞏcm
)
• Remote sensing connection
1) Connect "+S" terminal (Pin No.2) to "+" output terminal of load with wires.
2) Connect "S" terminal (Pin No.6) to "" output terminal of load with wires.
(Sensing lines shall be twisted.)
*If the remote sensing terminals are opened, the output will rise and OVP will operate.
8/28