![TDK-Lambda GXE600 Series Instruction Manual Download Page 27](http://html2.mh-extra.com/html/tdk-lambda/gxe600-series/gxe600-series_instruction-manual_4196959027.webp)
INSTRUCTION MANUAL
GXE600 Series
TDKLambda
<Page>
8. Wiring Method
(1) The output load line and input line shall be separated, and use all lines as thick and short as possible to make
lower impedance. The output load line and input line shall be twisted or use shielded wire to improve noise
sensitivity.
(2) Remote sensing lines and remote ON/OFF control lines shall be twisted and separated from the output lines.
(3) Noise can be reduced by attaching a capacitor to the load terminals.
(4) The recommended wire type, torque and crimptype terminal :
Note : Recommended wire type and crimptype terminal vary depending
on use conditions. Choice most appropriate wire type and
crimptype terminal by referring to wire maker recommended
allowable current and voltage drop.
9.The life expectancy
The life of the power supply depends on the life of the builtin aluminum electrolytic capacitor. The life is
described in reliability data.
The life of the aluminum electrolytic capacitor varies depending on the method of mounting the power supply,
the load current and the ambient temperature. Please refer to “Electrolytic Capacitor Lifetime”.
Please do not use the product which passed over the life expectancy. There is a risk of unexpected output
shutdown and specifications might not be satisfied.
Please contact us for maintenance or exchange the product which passed over the life expectancy.
10. External Fuse Rating
Refer to the following fuse rating when selecting the external input fuse.
Surge current flows when input turn on. Use slowblow fuse or timelug fuse. Fastblow fuse cannot be used.
Fuse rating is specified by inrush current value at input turn on.
Do not select the fuse according to actual input current (rms.) values.
GXE600 : 12.5A
27/28
D
(M AX)
t
(MAX)
M ounting piecs
(M AX)
1.0mm
1piece
0.8mm
2pieces
Output terminal M 4 Screws
1.2Nꞏm (12.0kgfꞏcm) ~ 1.6Nꞏm (16.3kgfꞏcm)
M odel
Recommended
Wire
Recommended torque
Recommended crimptype terminal
GXE600
AWG1222
Input terminal M 3.5 Screws
1.0Nꞏm (10.2kgfꞏcm ~ 1.6Nꞏm (16.3kgfꞏcm)
8.1mm