Forced air cooling
Use so that both of A. and B. shall be satisfied.
A : Derating is necessary to
output current
in case of ambient temperature more than 50°C.
B : Derating is unnecessary to
output power
in input voltage range 85265VAC.
For example, in case of input voltage 100VAC and ambient temperature 60°C at 24V model.
According to A. ambient temperature derating,
output current limit
is 75% (18.75A).
①
According to B. input voltage derating is unnecessary,
output power limit
is 600W.
②
⇒
If Vo=28.8V (max.), the derating is determined by
output current
(18.75A)
①
.
Because output power is less than 600W (28.8V x 18.75A = 540W).
In forced air condition, the entire components shall be cooled.
Temperature of L2 and L5 need to be less than 85 °C.
As reference, set wind velocity at 1.0m/s (height of space at 50mm. our test condition).
Choke coil allowable Max. temperature
Monitoring point
L2: Top of core case
L5: Side of core
25/28
Allowable Max. temperature
L2
L5
85°C
85°C
L5
L2
Forced air cooling
Ta
(°C)
20
≦
Ta
≦
+50
70
Input Voltage
(VAC)
85
~
265
100% (600W)
B : Output Power vs. Input Voltage
Output Power
A : Output Current vs. Ta
Forced air cooling
100
50
Output Current (%)
0
20
40
60
80
100
120
20 10 0
10 20 30 40 50 60 70 80
O
ut
p
ut
C
ur
re
nt
(%
)
Ta (
o
C
)
0
20
40
60
80
100
120
85
115
145
175
205
235
265
O
ut
p
ut
P
ow
er
(%
)
Input Voltage (VAC)