Multiple contours occur.
Image reflections, so called ”ghost
images“ occur due to open lines.
The video strand is not closed.
Please insert the terminating re-
sistor at the last device of the
strand.
Contours of the second image
are visible.
Two video sources interfere.
Please remove the second video
source from the strand.
If necessary, connect this second
video source via a video switch to
the existing TCS:BUS.
No image. Image switch button
does not respond when press-
ing.
No signal present.
Connect the monitor in front of the
video switch and check whether a
signal is available here.
Measure the voltage between P and
b.
The voltage usually is about 24 V.
If this is not the case, please check
the power supply of the BUS.
Not both wires of the video BUS
are connected.
Please check the connection of the
video connector in the video module
of the IMM.
The video image turns white
after a while. When switching
the supply voltage off and on
again, the signal will reappear.
After a while, the video image
turns white again.
Thermal defect of the outdoor
cam-era.
Die V1-Ader des Video-Busses hat
einen Schluss auf die P- oder die
b-Ader. Dadurch fließt ein unzuläs-
sig erhöhter Strom.
Bitte die Verkabelung auf Schlüsse
überprüfen.
The camera is defect.
The camera FVK2200 (color variant
of VKM10) is defect. Around. 2% of
all cameras has this defect. Chang-
ing the camera corrects the prob-
lem.
Cleaning
!
Avoid water entering the device!
Do not use any abrasive detergents!
Clean the device with a dry or slightly moist cloth.
Remove stronger stains with a mild plastic cleaner.