Contents                                   

Description

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Features

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Mounting

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Wiring

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

Setup

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Programming

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4

Setting Clock & Schedule

. . . . . . . . . . . . . . . . . . . . . . .

7

Operation

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

Checkout & Troubleshooting

  . . . . . . . . . . . . . . . . . . . .

11

LED Description

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13

Limiting Occupant Access  . . . . . . . . . . . . . . . . . . . . . . 13

User’s Guide

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14

Mounting                                 

The SZ1024 and SZ1033  are designed for wall mounting 

using two #6 sheet metal screws, either over a horizontally 

installed 2” x 4” junction box, or directly to block or drywall. 
For best results, the thermostat should be mounted on an 

interior wall which reflects normal room environment, at a 

height of approximately five feet from the floor. Avoid areas 

exposed to direct sunlight, unusual heat sources, open 

doors and windows, or unventilated locations. 
If using a remote room sensor, it should be mounted in   

the manner described above. The thermostat may then    

be mounted in an area which is accessible for adjusting   

its settings. 

Caution

: Remove power from thermostat prior   

to mounting.

Product Manual           

Description                             

The SZ1024 and SZ1033 are microprocessor-based 

programmable thermostats designed for heat pump 

applications. The SZ1024 features a 7-day time clock, 

while the SZ1033 and features a 365-day time clock. 

Features                                

•  Stand-alone or network operation

•  Adjustable delay on power-up and start-up for soft 

starts

•  P+ I control option

•  Smart Recovery 

•  No battery backup required

•  Built in HVAC equipment protection

•  32-character LCD display

•  Six status LEDs 

•  Remote room sensing capability

•  User setpoint adjustment limits

•  Local and remote override capability

•  System and fan switching with access lockouts

•  Auxiliary time clock output (economizers)

•  Equipment monitoring inputs and indication

•  External time clock input 

•  Access to programming or schedule may be locked 

out or limited with the use of an access code

•  Fahrenheit or Celsius temperature display

•  Convertible to conventional mode in programming

R

        Communicating Thermostats

        Communicating Thermostats

SZ1024/SZ1033

Heat Pump Thermostats

Summary of Contents for SZ1024

Page 1: ...ch is accessible for adjusting its settings Caution Remove power from thermostat prior to mounting Product Manual Description The SZ1024 and SZ1033 are microprocessor based programmable thermostats de...

Page 2: ...r must be used to power the Superstat Several S Series ther mostats may be powered from the same transformer provided that the transformer has sufficient power Superstats require 8W 24 VAC Caution Do...

Page 3: ...ir sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1033 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order to lock the user...

Page 4: ...m setup SET UNOCCUPIED FAN MODE AUTO 11 program setup SET OCCUPIED FAN MODE ON 10 program setup USER ACCESS TO FAN MODE YES 9 program setup SET SYSTEM MODE AUTO 7 program setup USER ACCESS TO SYSTEM M...

Page 5: ...int for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Setpoint Screen Set the cool setpoint for this occupied period Occupied Cool Set...

Page 6: ...y P or add a time factor P I Time Clock Output Screen Choose whether the auxiliary output will be OPEN during occupied periods and closed during unoccupied periods or CLOSED during occupied periods an...

Page 7: ...4 33 SZ1022 31 Compressor 1 Becomes Cool 1 Compressor 2 Becomes Cool 2 Aux Heat 1 Becomes Heat 1 Aux Heat 2 Becomes Heat 2 Emergency Heat Mode does not exist Aux Heat 1 Must be enabled Step 24 for hea...

Page 8: ...bled using the software the override also activates in occu pied mode and takes the thermostat into unoccupied mode In either case you are able to view the time remaining in the override period both w...

Page 9: ...ges will be turned off and will remain off until the discharge air temperature falls 3 below that limit If the LOW LIMIT is reached the fan and cooling stages will be turned off and will remain off un...

Page 10: ...IARY OUTPUT An auxiliary relay output is available to output a signal based on the occupancy status It is commonly used with an economizer minimum position control or to signal an outdoor air damper t...

Page 11: ...e reading Press the WARMER up button The setpoint adjustment screen should now be showing Press the WARMER button until the heating setpoint is greater than the current temperature by at least five de...

Page 12: ...the wiring Short terminals R to W1 W2 Y1 Y2 or B O and see if the heating or cooling comes on This is a check for a mechanical relay failure Both Heating and Cooling Are On If this occurs there are t...

Page 13: ...fan O ccupied Heating Cooling Fan Serv ice Program CO OLER W ARM ER Data switch service status system switch program setup clock setup override 11 19 01 Main Monitoring Screen Press the service butto...

Page 14: ...s described in the setup section User s Guide Inside the hinged door of the thermostat is the SuperstatTM User s Guide This guide is designed to assist the installer in explaining to the user how to o...