Monitor mode:

 the digital input acts as a monitor for the 

DI and has no other function.

ASTRONOMICAL TIME

The Astronomical time function may be setup on any of 

the channels. It controls and turns off the enabled light 

channel for the daylight period form sunrise to sunset. 

The following diagram illustrates the typical application of 

this capability.

To setup astronomical time, enter the Latitude and Lon-

gitude parameters for the location being controlled. Also 

enter the time offset from GMT (Greenwich Mean Time). 

For example, the USA Central Standard time zone is 

offset -360 minutes from GMT. Madison, Wisconsin, USA 

is at 43° 5 minutes North (+) Latitude and 98° 30 minutes 

west (+) Longitude. The GMT Offset range is + 720 Min-

utes. Also click the box if applying daylight savings time to 

the astronomical time calculation.

Next, select the channel(s) that should have the astro-

nomical time function and click the Enable box. This is 

done in the Schedule section of the page.

Note: For non-North American Daylight Saving time set 

the manual DLS (Day Light Saving) time.

CHANNEL OCCUPANT OVERRIDE

This is the number of minutes from 0 to 255 (4 hr, 15 min) 

which the controller will bring a system that is Off to On 

when its override button is pressed. This time can be dif-

ferent for each channel.

Occupied Override:

 Select whether to allow an occupied 

override and if so, whether it will be a schedule or chan-

nel override.

HOLIDAY VANISHING

Choose whether to enable the Holiday Vanishing Feature. 

If checked, the controller will make the number of days 

for a holiday 0 after the holiday is over. This will keep 

the holiday from occurring in subsequent years if it is not 

reprogrammed.

DIGITAL INPUT DELAY/FILTER

Enable the Digital Input Delay if you want the Digital Input 

to be present for 15 seconds before it takes effect. This 

can prevent cycling. Note, this delay if selected, will apply 

to all eight channels. 

POWER DOWN PERIOD

If the controller loses power, it can remember which chan-

nels have been overridden and how much time is remain-

ing in each override period. This is the amount of con-

tinuous power loss time in minutes where the controller  

will remember the override status'. If the controller loses 

power for longer than this period, the override buttons will 

have to be pressed again as necessary.

INPUT VOLTAGE

The input voltage is monitored. The calibration factor is 

used to scale the controller's 24 VAC power input to the 

appropriate line voltage. For example, if the line voltage 

is 120 VAC and the SLQ218 power input is 24 VAC, then 

the calibration factor is 5.0. If the line voltage is 120 VAC 

and the controller power input is 27 VAC, then the calibra-

tion factor is 4.4 If the line voltage is 277 VAC and the 

SLQ218 power input is 24 VAC, then the calibration factor 

is 11.5.

DAYLIGHT SAVING TIME

If Daylight saving is used, simply enable the "Daylight 

Saving Time"  option within the software and enter the 

starting month + week and the ending month + week.

Summary of Contents for QWL 3.1 2 Series

Page 1: ... Astronomical clock External time clock or occupancy sensor input for each channel Channel status LEDs Selectable normally open or normally closed relays Built in 2 Amp relays with hand off auto switches Contents Description 1 Features 1 Factory IP Network Address Configuration 1 Mounting 2 Wiring 2 RS 485 Controller Network Wiring Setup 3 Gateway Configuration Page 4 Commissioning Tools 5 Program...

Page 2: ...ev 2 Series Panel accepts two 0 to 5 VDC inputs 8 dry contact digital inputs and 4 pulse meter inputs POWERING THE QWL 3 1 REV 2 SERIES PANEL The QWL 3 1 Rev 2 Series Panel is powered from a 120VAC 60HZ to 12VDC power supply module includ ed The QWL 3 1 Rev 2 Series Panel is designed to contain 24 VAC devices and wiring ONLY No line voltage 120 VAC or greater is to be installed within this panel M...

Page 3: ...ev 2 Series Panel 4 NOTES 1 If using more than 64 control lers use additional QD1010 adapters 2 Each controller must use the same baud rate and be assigned a unique address B wires If the QWL 3 1 Rev 2 Series Panel will be at one end of the network hard wire a 120 Ω terminating resistor across the A and B terminals at the QWL 3 1 Rev 2 Series Panel See 1 below If the QWL 3 1 Rev 2 Series Panel wil...

Page 4: ...elect a Controller Network Polling Cycle time for the QWL 3 1 Rev 2 Series Panel This is the time interval that the unit will poll the entire network of controllers on all ports The default setting is 1 min ute Select whether to allow caching the host name via DNS Typically this is left unchecked Select how often the QWL 3 1 Rev 2 Series Panel connects to the central server Typically this is set t...

Page 5: ...ontrol the security of the gateway within the QWL 3 1 Rev 2 Series Panel and whether or not it can be accessed through the web interface Enabling Secure Mode disables all web interfaces including the configuration page and requires a specially configured USB flash drive or TCS Technical Support access to the QWL Panel if it is online with Ubiquity central server to unlock it Also the default login...

Page 6: ...eight independent channels each with its own schedule If the occupied or ON time for a particular day is from 8 00AM to 5 00PM In the schedule enter 8 00 to 17 00 Within the Ubiquity programming page the desired schedule is simply selected from the drop down menu for each channel If the desired schedule is not shown in the drop down new schedules can be created or existing schedules can be edited ...

Page 7: ...ing high limit Select whether you want the time clock output Digital Output Mode to be Normally Open or Normally Closed during on periods The Channel Power Threshold is basically a setpoint to which AI2 is compared to determine when to turn off the selected channel s The Channel Power Hysteresis is a buffer value which prevents the channel from cycling off on prematurely For example if the AI2 inp...

Page 8: ...d override and if so whether it will be a schedule or chan nel override HOLIDAY VANISHING Choose whether to enable the Holiday Vanishing Feature If checked the controller will make the number of days for a holiday 0 after the holiday is over This will keep the holiday from occurring in subsequent years if it is not reprogrammed DIGITAL INPUT DELAY FILTER Enable the Digital Input Delay if you want ...

Page 9: ...nality can be mimicked by using a Meter Multiplier value of 2 In the following picture both Type A and C are shown Three pulses are shown labelled 1 2 and 3 Notice how the Type A output closes and opens for each pulse where the Type C output simply changes state If you have a Type C device 3 terminals KYZ you will need to double the multiplier The SEQ100 only counts the contact closures for the K ...

Page 10: ...o reboot the entire QWL 3 1 Rev 2 series panel This is accomplished by pushing and holding the button for 5 7 seconds Note During a reboot the lights associated with the Lighting Module of this product could go out it is recommended that you open the panel and place the Hand Off Auto switch for the corresponding channel in the Hand position to ensure that the lights that should be on remain on CPU...

Page 11: ...pically a problem with wir ing Check wiring Make sure that communication wir ing runs are at least 5 away from fluorescent lights motors etc Make sure that all controllers on a net work have a unique address Make sure that the A and B wires are not switched or shorted Make sure that there is no stray voltage on the A and B wires B to A should measure between 0 5 VDC and 3 6 VDC B to A should measu...

Reviews: