Energy Hub User Manual
12
OR
➢
Dry contact 3
When the dry contact 3 connect to the DRY CONTACT of C12, it will control the output of C12. If the
system is turned off
,
the output of C12 will be closed via Dry contact3. If the system is turned on
and SOC
≥
5% (5%~50% can be set), the output of C12 will be turned on via Dry Contact3, SOC
≤
0% (0%~45% can be set, SOC of the C12 output is turned on
≥
SOC of the C12 output is turned off
+5%) , the output of C12 will be turned off via Dry Contact3.
4) Regular inspections
In order for the BMS to calculate the SOC of lithium battery more accurately and eliminate the
cumulative error of SOC, it is recommended to complete a full discharge (discharge to 0% SOC)
and a full charge (charge to 100% SOC) every 3 months.