54
7.3.2 CM Secondary Connections
Figure 40
Terminal arrangement of the CM
The CM_16_1 has secondary connectors (as shown below).
CM relay functionality:
• Relay 1 - “ISM main contact position” relay;
• Relay 2 - “Ready” relay;
• Relay 3 - “Malfunction or Loss of Auxiliary Supply” relay
The “ISM main contact position“ relay maintains its state (1 NO and 1 NC contacts with common point) after the
CM power supply disconnection.
Relay functionality and the number of relays which share the same functionality can be changed upon request.
Please contact the nearest Tavrida Electric sales representative for more information.
The CM is connected only to the ISM actuator coil circuits. The position of the ISM main contacts is determined by
detecting the ISM coil inductance level. The CM “ISM main contact position” relay indicates the result.
Table 18 - CM Terminal Arrangement
XT1
XT3
Terminal No.
Connection
Terminal No.
Connection
1
Power supply input (+)
1
Actuator coil output
2
Power supply input (-)
2
Actuator coil output
3
Relay output 1 NO
4
Relay output 1 Com
5
Relay output 1 NC
6
Relay output 2 NO
7
Relay output 2 Com
8
Relay output 2 NC
9
Relay output 3 NO
10
Relay output 3 Com
11
Relay output 3 NC
12
Close dry input
13
Close dry input
14
Trip dry input
15
Trip dry input
Summary of Contents for VCB15
Page 2: ......
Page 4: ......
Page 5: ...1 Introduction...
Page 9: ...2 Presentation...
Page 11: ...3 Product Coding...
Page 23: ...4 Technical Parameters...
Page 33: ...5 Design and Operation...
Page 42: ......
Page 43: ...6 Functionality...
Page 48: ......
Page 49: ...7 Application Notes...
Page 56: ......
Page 57: ...Appendix 1 Type Tests...
Page 61: ...Appendix 2 Withdrawable VCB Package Dimensions...
Page 63: ...Appendix 3 Overall Drawings...
Page 65: ...65 VCB15_LD8_16D 17 5kV 800 A PCD 210 mm weight 76 kg Lmax 677 mm Wmax 682 mm Hmax 528 mm...
Page 69: ...69 VCB15_MD1_16D 17 5kV 1250 A PCD 210 mm weight 74 kg Lmax 677 mm Wmax 682 mm Hmax 515 mm...
Page 73: ...73 VCB15_HD1_16D 17 5kV 2500 A PCD 275 mm weight 140 kg Lmax 656 5 mm Wmax 882 mm Hmax 704 mm...
Page 74: ...74 VCB15_HD1_16D 17 5kV 3150 A PCD 275 mm weight 158 kg Lmax 656 5 mm Wmax 882 mm Hmax 704 mm...
Page 101: ...101 3 n 3B 3B 24 kV 1250 A fixed contact 2000 A fixed contact...
Page 102: ...102 3150 A fixed contact...
Page 103: ...Appendix 4 Secondary Schemes...
Page 104: ...104 VCB15_LD8_16D with Plastic Plug...
Page 105: ...105 VCB15_LD8_16D with Metal Plug...
Page 113: ......
Page 114: ......
Page 115: ......