Table 12 - VCB15 Technical Parameters
Type
VCB15_LD8
VCB15_MD1
VCB15_HD1
“Close” and “Trip” Dry Contacts Inputs of the CM
Output voltage
≥ 30 V
Contacts closed current
≥ 50 mA
Steady state current
≥ 5 mA
1) The rating depends on the metal-enclosed switchgear ventilation. Temperature rise type test at 2500 A in Cradle was successfully passed in KEMA.
2) The information in brackets refers to the national Chinese standards GB1984-2003 at an installation altitude of 1000 m maximum.
3) At 34% DC component.
4) At 40% DC component.
5) Smaller timing on request.
6) The number of sequential Close-Trip operations with a 10 second interval should not exceed 10. The number of Close-Trip operations should not exceed 60 per hour. Sequence of 10s Close-Trip
operations can be repeated only after 260 s pause.
7) Isolation resistance check is not applicable for “Actuator Coil” circuits of CM.
8) Up to an installation altitude of 1000 m above sea level. Above 1000m, the external insulation measurement of the ISM must be increased by the atmospheric correction factor Ka according to IEC
62271-1 compared to the insulation measurement at sea level. The maximum allowed altitude is 2000 m above sea level.
9) Overall dimensions of VCB are provided in “Appendix 3. Overall Drawings”.
10) At 5 min short-term duty. Continuous current – 5 A.
11) In case of dry contacts “close” and “trip” are open.
12) At Cos j >0.66.
13) At Cos j >0.33.
Summary of Contents for VCB15
Page 2: ......
Page 4: ......
Page 5: ...1 Introduction...
Page 9: ...2 Presentation...
Page 11: ...3 Product Coding...
Page 23: ...4 Technical Parameters...
Page 33: ...5 Design and Operation...
Page 42: ......
Page 43: ...6 Functionality...
Page 48: ......
Page 49: ...7 Application Notes...
Page 56: ......
Page 57: ...Appendix 1 Type Tests...
Page 61: ...Appendix 2 Withdrawable VCB Package Dimensions...
Page 63: ...Appendix 3 Overall Drawings...
Page 65: ...65 VCB15_LD8_16D 17 5kV 800 A PCD 210 mm weight 76 kg Lmax 677 mm Wmax 682 mm Hmax 528 mm...
Page 69: ...69 VCB15_MD1_16D 17 5kV 1250 A PCD 210 mm weight 74 kg Lmax 677 mm Wmax 682 mm Hmax 515 mm...
Page 73: ...73 VCB15_HD1_16D 17 5kV 2500 A PCD 275 mm weight 140 kg Lmax 656 5 mm Wmax 882 mm Hmax 704 mm...
Page 74: ...74 VCB15_HD1_16D 17 5kV 3150 A PCD 275 mm weight 158 kg Lmax 656 5 mm Wmax 882 mm Hmax 704 mm...
Page 101: ...101 3 n 3B 3B 24 kV 1250 A fixed contact 2000 A fixed contact...
Page 102: ...102 3150 A fixed contact...
Page 103: ...Appendix 4 Secondary Schemes...
Page 104: ...104 VCB15_LD8_16D with Plastic Plug...
Page 105: ...105 VCB15_LD8_16D with Metal Plug...
Page 113: ......
Page 114: ......
Page 115: ......