26
Table 12 - VCB15 Technical Parameters
Type
VCB15_LD8
VCB15_MD1
VCB15_HD1
Preparation time for the close operation of the CM after a previous close operation
≤ 10 s
Preparation time for the trip operation of the CM after switching on the auxiliary power supply
≤ 0.1 s
Trip capability after failure of the auxiliary power supply
CM Supply Voltage
Rated range of supply voltage of CM_16_1(Par1_60.2_Par2_Par3_Par4_Par5)
24 V to 60 V DC
Rated range of supply voltage of CM_16_1(Par1_220.2_Par3_Par4_Par5)
110 V to 220 V AC/DC
Operating range (80-120%) of CM_16_1(Par1_60.2_Par3_Par4_Par5)
19 V to 72 V DC
Operating range (80-120%) of CM_16_1(Par1_220.2_Par3_Par4_Par5)
85 V to 265 V AC/DC
CM Power Consumption
Charging the close and trip capacitors of CM_16_1(Par1_60.2_Par3_Par4_Par5)
≤ 25 W
Charging the close and trip capacitors of CM_16_1(Par1_220.2_Par3_Par4_Par5)
≤ 37 W DC
Permanent power consumption (standby) of CM_16_1(Par1_60.2_Par3_Par4_Par5)
≤ 5 W
Permanent power consumption (standby) of CM_16_1(Par1_220.2_Par3_Par4_Par5)
≤ 5 W DC
Inrush current of CM_16_1(Par1_60.2_Par3_Par4_Par5) with discharged capacitors
≤ 120 A
Inrush current of CM_16_1(Par1_220.2_Par3_Par4_Par5) with discharged capacitors
≤ 18 A
Inrush time constant of CM_16_1(Par1_60.2_Par3_Par4_Par5) with discharged capacitors
≤ 0.5 ms
Inrush time constant of CM_16_1(Par1_220.2_Par3_Par4_Par5) with discharged capacitors
≤ 4 ms
Design/Switching Capacity of CM Inbuilt Relays
Number of relays in CM
3
Number of available contacts for one relay
1 NO + 1 NC with common point
Rated voltage
240 V
Rated current AC
16 A
Maximum breaking power AC
4000 VA
Maximum switching current 250 V DC
0.35 A
Maximum switching current 125 V DC
0.45 A
Maximum switching current 48 V DC
1.3 A
Maximum switching current 24 V DC
12 A
Switching time
5 ms
Summary of Contents for VCB15
Page 2: ......
Page 4: ......
Page 5: ...1 Introduction...
Page 9: ...2 Presentation...
Page 11: ...3 Product Coding...
Page 23: ...4 Technical Parameters...
Page 33: ...5 Design and Operation...
Page 42: ......
Page 43: ...6 Functionality...
Page 48: ......
Page 49: ...7 Application Notes...
Page 56: ......
Page 57: ...Appendix 1 Type Tests...
Page 61: ...Appendix 2 Withdrawable VCB Package Dimensions...
Page 63: ...Appendix 3 Overall Drawings...
Page 65: ...65 VCB15_LD8_16D 17 5kV 800 A PCD 210 mm weight 76 kg Lmax 677 mm Wmax 682 mm Hmax 528 mm...
Page 69: ...69 VCB15_MD1_16D 17 5kV 1250 A PCD 210 mm weight 74 kg Lmax 677 mm Wmax 682 mm Hmax 515 mm...
Page 73: ...73 VCB15_HD1_16D 17 5kV 2500 A PCD 275 mm weight 140 kg Lmax 656 5 mm Wmax 882 mm Hmax 704 mm...
Page 74: ...74 VCB15_HD1_16D 17 5kV 3150 A PCD 275 mm weight 158 kg Lmax 656 5 mm Wmax 882 mm Hmax 704 mm...
Page 101: ...101 3 n 3B 3B 24 kV 1250 A fixed contact 2000 A fixed contact...
Page 102: ...102 3150 A fixed contact...
Page 103: ...Appendix 4 Secondary Schemes...
Page 104: ...104 VCB15_LD8_16D with Plastic Plug...
Page 105: ...105 VCB15_LD8_16D with Metal Plug...
Page 113: ......
Page 114: ......
Page 115: ......