15
2
2
The rating plates for the CM1501 series contain the following information (Figure 16):
Breaker Control Module
Model CM_16_1(60)
Power Supply Input
19-72
25 W for 10s (charging)
5 W steady state
Input must be
protected by a two pole
miniature circuit breaker
rated: 4A, type B or C
Fault / Ready Relays
Max 240 16A
See circuit breaker
applications manual for
detailed information and
DC load break capacity.
Operating Conditions
-40C to +55C ambient
IP40 degree of protection
Operating Duty
O-0.3s-CO-10s-CO-10s
Conforms to
UL STD 508
Certified to
CAN/CSA-22.2 No.
142-M1987
Tavrida Electric North America
1105 Cliveden Ave, Delta, BC, Canada
1-866-551-8362
Made in Russia
4000068
1
2
3
4
5
4
6
7
8
9
1. Model type
2. Auxiliary power supply min / max
3. Power consumption
4. Warning notes
5. Output contact maximum voltage / current
The rating plate for the CM16 series contain the following information (Figure 17):
1
2
3
4
5
6
7
8
9
The CM_16 has an additional label for factory programmable settings (Figure 18); see page 31 for detailed
information on the settings functions.
1
2
1. Settings
2. QR code (scannable settings code)
3. Applicable breaker type
3
6. Operating conditions
7. Operating duty cycle
8. NRTL listing / conformance mark
9. Contact information
Figure 16
Figure 17
Figure 18
Summary of Contents for ISM15_LD_1 Series
Page 2: ......
Page 6: ...6 1 Introduction 1...
Page 11: ...11 2 Receiving Handling and Storage...
Page 17: ...17 Ins tallation 3...
Page 34: ...34 4 Switching and Control Functions 4...
Page 38: ...38 5 Commiss ioning Operation Maintenance 5...
Page 41: ...41 6 Signalling 6...
Page 45: ...45 6 Product Line 6...
Page 47: ...47 7 Dimens ions and Weights 7...
Page 53: ...53 8 Circuit Diagrams 8...
Page 54: ...54 ISM_LD with CM_16_1 Control Module 8...
Page 55: ...55 8 ISM_LD with CM_1501_01 Control Module...
Page 56: ...56 9 Technical Data 9...
Page 62: ...62 9 9...
Page 63: ...63 10 Regulations and Ambient Conditions 10...
Page 65: ...65 11 Legal Information 11...
Page 69: ...69 11 Date...