36
4
Variant 1
- In the CM close command circuit
Variant 2
- In the ISM auxiliary switch circuit
Variant 3
- In the close command circuit and in the ISM position switch circuit
If despite effective electrical closing lock-out a close attempt is made, the Malfunction LED will blink 2 times (see
malfunction indication table, page 43). The reason for the malfunction must be eliminated to abolish the electrical
closing lock-out and to activate the close readiness.
ISM Forced Trip by an Undervoltage Relay (Optional -
CM_1501 Series)
In case the ISM shall trip due to the auxiliary power supply voltage droping below the minimum value an additional
undervoltage relay is required (not part of the scope of supply). The trip contact of the undervoltage relay shall be
integrated into the dry contact trip command circuit of the CM. If the CM was ready for operation before the voltage
dropped below the minimum value, tripping of the ISM is possible within 30 s after the voltage dropped below the
minimum level.
Note that for undervoltage trip functions it is recommended to use the CM_16 series where possible due to the more
flexible capability it provides for reclosing and UV trip delay.
4
4
Output to Magnetic Actuator and Input for ISM Pos ition
Indication
The cables between the ISM and CMnas well as the coils of the magnetic actuator are monitored permanently (see
malfunction indication table, page 43). Internally at the auxiliary switch inputs of the CM_1501 230 V DC is applied
for the ISM auxiliary switch S13. The CM_16 series does not utilize the auxiliary switch; instead the impedence of the
actuator coils is monitored for position of the breaker as well as loss of connection.
4
Operations Counter
Depending on site or switchgear requirements, a method of recording circuit breaker close / open operations may
be needed. The preferred method of tracking operations is to utilize the breaker wear monitor available on most
modern didgitical relays, which will calculate the remaining lifetime based on number of operations and switching
interruptions. Alternatively, a pulse counter per the table below can be ordered from Tavrida that will indicate the
number of mechanical operations. These counters can be wired to any of the 52a auxiliary contacts on the breaker.
Auxiliary Voltage
Pulse Counter Part Number
24VDC
5RSI62.2 24C
48VDC
5RSI62.2 48C
120VAC
5RSI62.2 110
125VDC
5RSI62.2 110C
220VAC
5RSI62.2 220
Summary of Contents for ISM15_LD_1 Series
Page 2: ......
Page 6: ...6 1 Introduction 1...
Page 11: ...11 2 Receiving Handling and Storage...
Page 17: ...17 Ins tallation 3...
Page 34: ...34 4 Switching and Control Functions 4...
Page 38: ...38 5 Commiss ioning Operation Maintenance 5...
Page 41: ...41 6 Signalling 6...
Page 45: ...45 6 Product Line 6...
Page 47: ...47 7 Dimens ions and Weights 7...
Page 53: ...53 8 Circuit Diagrams 8...
Page 54: ...54 ISM_LD with CM_16_1 Control Module 8...
Page 55: ...55 8 ISM_LD with CM_1501_01 Control Module...
Page 56: ...56 9 Technical Data 9...
Page 62: ...62 9 9...
Page 63: ...63 10 Regulations and Ambient Conditions 10...
Page 65: ...65 11 Legal Information 11...
Page 69: ...69 11 Date...