background image

11

14

10 Parameters

9.5 Screen of the mixer operation in the floor system

Fig.84 Screen of the mixer operation (heater, floor system)

!

Direction of valve movement"

means opening the valve in direction of increasing

temperature at the output (respectively

- lowering). If the valve drive runs, the arrow blinks. Lack

of the arrow means in the next cycle the valve remains motionless.

Icons of
additional
data

Temperature
behind the mixer

Icon of
MIXER screen

Preset
temperature

Direction
of valve
movement

Mixer
pump

F2=manual
operation

F1=setting
the basic
parameters

The screen appears at the setting <60>(

ModeMIXER

)=FLOOR

!

In the SUMMER mode (mixer turned off) the preset temperature doesn't show up.

Pressing the F1 button enables the change of the basic parameters of the mixer as follows:

# <62p> "TempFLOOR" the preset temperature of the mixer.

By pressing the F2 button you can transition to the manual operation in order to test the correctness of
mounting and operation of the valve.

LEVEL OF PARAMETERS 1

No

NAME

RANGE

SETTING

FUNCTION

10

ł

OFF /

ON /

ON+

ALARM

11

Language

Polish/

English /
German

Polish

Choose of language of messages

13

OFF/

ON

OFF

15

-

10%

2X

DEFAULT

Signal

ZA

Ł

+

ALARM

OFF- turning off sound alarm
ON - turning on the sound
ON+ALARM- turning on the sound and alarms

0

25%

boiler

20

TempBOILER

-

40...90

o

C

55

o

C

29

Temp-

THERMOST

AT

40...85

o

C

45

o

C

Backlit LCD

Minimum
backlit LCD

OFF - backlit display is active for 2mins since last
pressing a button
ON - backlit display is active always when the controller

is on.

Switching off the backlighting means it gets the value

defined by the next parameter <15>

Minimum LCD backlighting (it's valid at the negative LCD).
The value "0%" means a full switch-off

Preset temperature of the boiler kept up by
the controller

Preset temperature of the boiler with the room
thermostat, that is, the temperature to which
the controller swirches over the boiler in case if
the room thermostat decides about switching off
the heating. ATTENTION: this parameter
has to be higher than the switch-off temperature
of the boiler.

3X

blower

33

Break-
SCAVENGE

-

2

10min

3min

Pause of the scavenge

34 Time-

SCAVENGE

5

60s

10s

Time of the scavenge

35

Efficiency-
SCAVENGE

50..100%

100%

Maximum efficiency of the blower

achieved at scavenging

4X

pumps

5X

WAW

50

ModeWAW

OFF/

SUMMER/

ON/

PRIO/

SPEC

ON

51

TmaxWAW

30...90

o

C

60

o

C

Maximum temperature of the WAW container
Exceeding it turns off the loading pump

52

TminWAW

30...90

o

C

50

o

C

53

TloadWAW

40...90

o

C

65

o

C

6X

mixer

62

Temp-

MIXER

20

90

o

C

40

o

C

Preset temperature of the mixer operating in
RETURN mode

62p

Temp-

FLOOR

20

40

o

C

25

o

C

OFF- loading the WAW container switched off
SUMMER - only loading the WAW, CH pump turned off
ON- normal operation of the WAW and CH pump
PRIO- WAW priority (during loading the CH pump runs
cyclically
SPEC- like PRIO, additionally while loading increasing
boiler temperature to the value of <53>

Minimum temperature of the WAW container
Exceeding it turns on the loading pump

Preset temperature of the boiler automatically set in case
of loading the WAW container in SPEC mode

Preset temperature of the mixer operating in
FLOOR mode

Summary of Contents for RT-14

Page 1: ...thermostat 94 C 230V 50Hz Power consumption without load 4W Max connection power 750W Operation conditions 0 50 C humidity10 90 no condensation Housing protection class IP41 Fuse 6 3A 250V P of blower...

Page 2: ...ILER 45min the temperature doesn t increase then the blower turns off an The given temperatures relate to the situation when the sensor of the flue gas is inactive After connecting the flue gas sensor...

Page 3: ...r our sole responsibility that the product Controller of the Heating System model RT 14 PN EN 55022 2011 EMC IT devices Characteristics of radioelectric noises Acceptable levels and measurement method...

Page 4: ...TimeStopPumpCH o o The controller protects the system from freezing automatically switches on the circulating pump if themeasuredtemperatureisbelow The controller realizes an after season rundown of t...

Page 5: ...the WAW pump afterloadingthecontainercausesthenormaloperationoftheCH pumptocomeback the pumps run as in PRIO mode Additionally during loading the container the presettemperatureoftheboileris raisedto6...

Page 6: ...ents onthecontrolpanel fig 8 The operation state is presented on the graphic display 2 The screens inform about the operation of devices temperature of sensors they make it possible to change the para...

Page 7: ...21 TempALARM_BOILER 61 TempALARM FLOOR o 9 2 Screen of boiler operation Thescreenfeaturescurrenttemperatureof theboilerandrotationof theblower Fig 82 Screen of boiler operation 18 WARNING WE INFORM T...

Page 8: ...ler in case of the room thermostat operation TempBOILER TempTHERMOSTAT 17 PASSWORD 9999 HAS CONSIDERABLE MEANING IT CAUSES THE REACTIVATION OF THE PREVIOUS PASSWORD IF PRESENT WITHOUT IT BEING DISCLOS...

Page 9: ...he cyclical run After that time the CH pump runs for 45secs Temperature hysteresis of turning on off the pumps The temperature difference between turning on and turning off the pumps It prevents often...

Page 10: ...60min 45min The time of keeping up the low boiler temperature after which the transition to the stop state follows 3X blower DEFAULT boiler 30 ADJUSTABLE 31 10 100 100 32 1 10 o C 2 o C 38 2 10 o C 5...

Page 11: ...ways when the controller is on Switching off the backlighting means it gets the value defined by the next parameter 15 Minimum LCD backlighting it s valid at the negative LCD The value 0 means a full...

Page 12: ...t Parameter value change Upper and lower change limit THE PARAMETERS ADJUST THE CONTROLLER TO THE FEATURES OF THE BOILER AND THE CH SYSTEM THEIR CHANGE SHOULD BE CONSULTED WITH THE PRODUCER OF THE BOI...

Reviews: