10 Parameters
9.5 Screen of the mixer operation in the floor system
Fig.84 Screen of the mixer operation (heater, floor system)
!
”
Direction of valve movement"
means opening the valve in direction of increasing
temperature at the output (respectively
- lowering). If the valve drive runs, the arrow blinks. Lack
of the arrow means in the next cycle the valve remains motionless.
↑
↓
Icons of
additional
data
Temperature
behind the mixer
Icon of
MIXER screen
Preset
temperature
Direction
of valve
movement
Mixer
pump
F2=manual
operation
F1=setting
the basic
parameters
The screen appears at the setting <60>(
”
ModeMIXER
”
)=FLOOR
!
In the SUMMER mode (mixer turned off) the preset temperature doesn't show up.
Pressing the F1 button enables the change of the basic parameters of the mixer as follows:
# <62p> "TempFLOOR" the preset temperature of the mixer.
By pressing the F2 button you can transition to the manual operation in order to test the correctness of
mounting and operation of the valve.
LEVEL OF PARAMETERS 1
No
NAME
RANGE
SETTING
FUNCTION
10
ł
OFF /
ON /
ON+
ALARM
11
Language
Polish/
English /
German
Polish
Choose of language of messages
13
OFF/
ON
OFF
15
-
10%
2X
DEFAULT
Signal
ZA
Ł
+
ALARM
OFF- turning off sound alarm
ON - turning on the sound
ON+ALARM- turning on the sound and alarms
0
…
25%
boiler
20
TempBOILER
-
40...90
o
C
55
o
C
29
Temp-
THERMOST
AT
40...85
o
C
45
o
C
Backlit LCD
Minimum
backlit LCD
OFF - backlit display is active for 2mins since last
pressing a button
ON - backlit display is active always when the controller
is on.
Switching off the backlighting means it gets the value
defined by the next parameter <15>
Minimum LCD backlighting (it's valid at the negative LCD).
The value "0%" means a full switch-off
Preset temperature of the boiler kept up by
the controller
Preset temperature of the boiler with the room
thermostat, that is, the temperature to which
the controller swirches over the boiler in case if
the room thermostat decides about switching off
the heating. ATTENTION: this parameter
has to be higher than the switch-off temperature
of the boiler.
3X
blower
33
Break-
SCAVENGE
-
2
…
10min
3min
Pause of the scavenge
34 Time-
SCAVENGE
5
…
60s
10s
Time of the scavenge
35
Efficiency-
SCAVENGE
50..100%
100%
Maximum efficiency of the blower
achieved at scavenging
4X
pumps
5X
WAW
50
ModeWAW
OFF/
SUMMER/
ON/
PRIO/
SPEC
ON
51
TmaxWAW
30...90
o
C
60
o
C
Maximum temperature of the WAW container
Exceeding it turns off the loading pump
52
TminWAW
30...90
o
C
50
o
C
53
TloadWAW
40...90
o
C
65
o
C
6X
mixer
62
Temp-
MIXER
20
…
90
o
C
40
o
C
Preset temperature of the mixer operating in
RETURN mode
62p
Temp-
FLOOR
20
…
40
o
C
25
o
C
OFF- loading the WAW container switched off
SUMMER - only loading the WAW, CH pump turned off
ON- normal operation of the WAW and CH pump
PRIO- WAW priority (during loading the CH pump runs
cyclically
SPEC- like PRIO, additionally while loading increasing
boiler temperature to the value of <53>
Minimum temperature of the WAW container
Exceeding it turns on the loading pump
Preset temperature of the boiler automatically set in case
of loading the WAW container in SPEC mode
Preset temperature of the mixer operating in
FLOOR mode