2

23

!
2 Boiler operation

!

!

2.1 Firing up/Damping under control of the flue gas sensor

!

2.2 Limiting the flue gas temperature

!
3 Hydraulic configurations of the controller.

3.1 Configuration without the mixing valve
!

The text <xx> indicates the parameter “xx” whose detailed description is in ch. 9

The controller regulates the central heating system with the fine coal boiler, in which by
controlling the efficiency of the blower the boiler temperature is changed.

The fine coal CH boiler operates in the following cykle: firing-up - operation - damping:

he controller turns on the blower. It causes firing up the fine coal and

gradual increase in temperature of the boiler. Reaching <22> TempSTOP_BOILER = 35 C
finishes the firing-up phase. The duration of the firing-up phase is limited up to 2 hours. If the
temperature doesn

t increase the controller switches over to the damping phase.

The controller skips the firing-up phase and automatically turns on the boiler if after switching on
the power the water temperature is above <22>.

the controller maintains the boiler temperature at the preset value. If

the boiler temperature is below the preset one the blower switches on (the rotations of the blower
are selected automatically). The increase in temperature above the preset one causes the blower
switched off. In that state the scavenges of the boiler are carried out (acc. to the settings) in order
to get rid of the combustion gas.
The temperature drop below <22> TempSTOP_BOILER=

<23> TimeSTOP_BOILER=45min the temperature doesn

t increase then the

blower turns off an

The given temperatures relate to the situation when the sensor of the flue gas is inactive.

After connecting the flue gas sensor the transition between the operation phases depends on the
temperature of the flue gas.

Connecting the flue gas sensor opens up the following additional functions of the controller:

Fast detection of the fired-up and damped state
Enhancing the combustion efficiency by limiting the temperature of the flue gas.

The parameters <24>, <24d> and <25> determine the fired-up and damped conditions.

The controller detects the fired-up state if the flue gas temperature is above <24>+ <24d>

(50 C+30 C=80 C)

Setting <24>=500 C turns off that function. The transition between phases is controlled by the

water temperature (<22> , <23>).

The parameters <36> , <36d>and<37> determine the limit of the flue gas temperature.

If the

temperature exceeds <36>=250 C then the blower efficiency is reduced to the

value <37>=40% (if it

s higher)

Temperature drop below <36>-<36d> (250 C 20 C=230 C) calls back the normal operation.

<36>=500 C turns off that function. There

s no reduction of the blower efficiency

The following hydraulic diagrams show the possible operation configurations of the controller.

<60>(

ModeMIXER

)=OFF

Phase I/Firing - up - t

In the phase II/Operation -

o

o

o

o

o

o

o

o

o

o

35 C starts

. If for

d the operation cycle of the boiler is completed.

The controller detects the damped state if the flue gas temperature is below <24>=50 C and

that state remains active for the time <25>=10min

flue gas

o

o

the phase III/Damping of

the Boiler

?
?

?

?

?

?

Setting

For this configuration you set

Admission

date

Realization

date

Signature

Remarks

Summary of Contents for RT-14

Page 1: ...thermostat 94 C 230V 50Hz Power consumption without load 4W Max connection power 750W Operation conditions 0 50 C humidity10 90 no condensation Housing protection class IP41 Fuse 6 3A 250V P of blower...

Page 2: ...ILER 45min the temperature doesn t increase then the blower turns off an The given temperatures relate to the situation when the sensor of the flue gas is inactive After connecting the flue gas sensor...

Page 3: ...r our sole responsibility that the product Controller of the Heating System model RT 14 PN EN 55022 2011 EMC IT devices Characteristics of radioelectric noises Acceptable levels and measurement method...

Page 4: ...TimeStopPumpCH o o The controller protects the system from freezing automatically switches on the circulating pump if themeasuredtemperatureisbelow The controller realizes an after season rundown of t...

Page 5: ...the WAW pump afterloadingthecontainercausesthenormaloperationoftheCH pumptocomeback the pumps run as in PRIO mode Additionally during loading the container the presettemperatureoftheboileris raisedto6...

Page 6: ...ents onthecontrolpanel fig 8 The operation state is presented on the graphic display 2 The screens inform about the operation of devices temperature of sensors they make it possible to change the para...

Page 7: ...21 TempALARM_BOILER 61 TempALARM FLOOR o 9 2 Screen of boiler operation Thescreenfeaturescurrenttemperatureof theboilerandrotationof theblower Fig 82 Screen of boiler operation 18 WARNING WE INFORM T...

Page 8: ...ler in case of the room thermostat operation TempBOILER TempTHERMOSTAT 17 PASSWORD 9999 HAS CONSIDERABLE MEANING IT CAUSES THE REACTIVATION OF THE PREVIOUS PASSWORD IF PRESENT WITHOUT IT BEING DISCLOS...

Page 9: ...he cyclical run After that time the CH pump runs for 45secs Temperature hysteresis of turning on off the pumps The temperature difference between turning on and turning off the pumps It prevents often...

Page 10: ...60min 45min The time of keeping up the low boiler temperature after which the transition to the stop state follows 3X blower DEFAULT boiler 30 ADJUSTABLE 31 10 100 100 32 1 10 o C 2 o C 38 2 10 o C 5...

Page 11: ...ways when the controller is on Switching off the backlighting means it gets the value defined by the next parameter 15 Minimum LCD backlighting it s valid at the negative LCD The value 0 means a full...

Page 12: ...t Parameter value change Upper and lower change limit THE PARAMETERS ADJUST THE CONTROLLER TO THE FEATURES OF THE BOILER AND THE CH SYSTEM THEIR CHANGE SHOULD BE CONSULTED WITH THE PRODUCER OF THE BOI...

Reviews: