©Copyright Task Force Tips LLC 2004-2020
14
LIY-200 November 5, 2020 Rev19
Figure 3.6E
Monsoon RC for Ladder
4.0 INSTALLATION
4.1 ELECTRICAL INSTALLATION
See Remote Control (RC) Monitor Electrical Controls Supplemental Instructions LIY-500.
4.2 STRUCTURAL REQUIREMENTS
The structure that the monitor is mounted to must withstand the internal
pressure of the monitor as well as shear and bending forces due to nozzle
reaction. Nozzle reaction can be as high as 1500 lbs (700 kg)(2000 gpm at
200 psi).
For flanged connections, the use of flat flanges without raised faces is
recommended. Use a ring gasket as defined in ASME 16.21 or ISO 7483.
Tighten flange bolts in an alternating sequence as shown below. Tighten
sequentially each bolt or stud three times to 30%, then 60%, and finally
100% of the specified torque. Tighten to a total of 76-80 ft-lb (100-110 N·m).
Table 4.2
WARNING
Reaction forces generated by master stream flows are capable of causing injury and property
damage if not properly supported. Monitors should be securely installed by qualified individuals.
• Mounting objects must be capable of withstanding maximum nozzle reaction force listed in
SPECIFICATIONS.
• The monitor must be securely mounted to rigid support members.
• Do not use flanges or pipe made from plastic for monitor mounting.
• Torque all fasteners to specified values.
FLANGE TYPE
OPTION #
OUTSIDE
DIAMETER
THICKNESS
BOLT HOLE
CIRCLE
# OF
BOLTS
SIZE OF
BOLTS
in
mm
in
mm
in
mm
in
mm
3” ANSI 125/150-DN80 PN20
1
7.5
190
0.75
20
6.0
152.5
4
5/8
16
4” ANSI 150-DN100 PN20
2/R
9.0
230
0.94
23
7.5
190
8
5/8
16
6” ANSI 150 Flange
3
10.9
277
1.0
25.4
9.5
241.3
8
5/8
16
DN80, PN16 Flange
4
7.9
200
0.87
22
6.3
160
8
5/8
16
DN100, PN16 Flange
5
8.7
220
0.87
22
7.1
180
8
5/8
16
5.8"
[147mm]
12.3"
[312mm]
18.1"
[459mm]
17.9"
[454mm]
13.4"
[341mm]
45°
90°
90°
LEFT
90°
RIGHT
6.4"
[163mm]
6.1"
[155mm]
12.5"
[318mm]
6.5"
[166mm]
SWING
RADIUS
1
3
2
4
1
5
3
7
2
6
4
8
Tighten Sequentially Each Bolt Three Times