4.7 ELEVATION TRAVEL STOPS
The range of elevation travel for the Monsoon Monitor is 90 degrees above horizontal to 45 degrees below zero. The elevation range
may be limited by installing the supplied stop bolts and adjustment disks at the locations as shown. Consult factory for other ranges. The
figures include installation notes.
Figure 4.7A
Elevation Travel Limits
Figure 4.7B
Elevation Travel Stop Locations
(C) 30° BELOW
HORIZTONAL
STOP BOLT
#Y4145
SET SCREW
#VT37-24SS250
(A) 30° ABOVE
HORIZTONAL
(B) 45° ABOVE
HORIZTONAL
Remove Set Screw and install Stop Bolt
to obtain desired travel limits.
Elevation travel with no Stop Bolts is
90° above and 45° below zero.