7
3.3 INLETS AND OUTLETS
The standard Monsoon Monitor inlet is CODE-RPF for direct connection to TFT's Extend-A-Gun RC4 (4 inch size). Monitor inlet CODE-
RLF is available for direct connection to Extend-A-Gun RC3 (3 inch size). The standard outlet is 3.5”-6 National Hose male. Various
other inlet and outlet adapters are available as shown in figure 3.3A.
Fig 3.3A
Inlets and Outlets
3” ANSI 150 (Y4410A)
OR
4” ANSI 150 (Y4415A)
OR
DN80 PN16 (Y4423A)
OR
DN100 PN16 (Y4425A)
3” BSP MALE (Y4420A)
OR
4” BSP MALE (Y4430A)
EXTEND-A-GUN RC3
OR
EXTEND-A-GUN RC4
3” NPT FMALE (Y4440NL)
OR
4” NPT FEMALE (Y4450NP)
CODE-RLF
OR
CODE-RPF
INLET
MONITOR MOUNTED
CONTROL STATION
3.5” BSP MALE (Y4330ABN)
3.5” NH MALE (STANDARD)
3.5” NPSH MALE (Y4330AIN)
4.0” BSP MALE (Y4334ABP)
FLANGE
SIZE
3” ANSI 150
4” ANSI 150
DN80 PN16
DN100 PN16
OUTSIDE
DIAMETER
7.50”
9.00”
200 mm
220 mm
THICKNESS
.75”
.94”
22 mm
22 mm
NUMBER
OF BOLTS
4
8
8
8
SIZE OF
BOLTS
5/8”
5/8”
16 mm
16 mm
TORQUE
ON BOLTS
76-80 FT-LBS
76-80 FT-LBS
100-110 NEWTON-METER
100-110 NEWTON-METER
BOLT HOLE
CIRCLE
6.00”
7.50”
160 mm
180 mm