5.1 PANEL MONITOR OPERATOR STATION (Y4E-RP)
This operator station allows the monitor to be controlled from a remote location. The installer will need to mount the operator station and connect the
cable to the monitor and power. The enclosure is designed to be recess mounted in a panel.
This operator station has extra power and communication terminal blocks available and can be used as a central location for terminating wires. In this
type of installation the monitor cable, the power cable, and possibly other operator station cables could be installed into this operator station. On the back
of this enclosure are extra strain relief fittings.
In many installations this operator station will also include the wiring connections for the wireless, joystick, or installer supplied toggle switches. A
terminal block is available for “UP, DOWN, LEFT, RIGHT, FOG, SS” inputs.
5.1.1 MOUNTING
Select proper operator location. Panel space required will be 5-5/8” x 8” (142 x 200mm). A depth of 3-1/2” (89mm) will be required
behind the panel. Additional space will be required where the cables exit the back of the enclosure. Refer to Figure 5.1.1 for cutout
dimensions.
Fig 5.1.1
Panel Mount Operator Station Cutout Dimensions
5.1.2 ELECTRICAL WIRING
See figure 5.0 for typical connections. The 4-conductor cable from the operator station needs to be connected to power (red & black)
and to the communication link (blue & white) from the monitor. Refer to Figure 5.1.2 for typical cable preparation. Be sure to tighten all
terminal block screws securely.
Fig 5.1.2
Typical Cable Preparation
5-1/8
(130 mm)
7-7/16
(190
mm)
5.2 TETHER MONITOR OPERATOR STATION (Y4E-CT-##)
This operator station will have a factory installed 4-conductor cable, which will act as a tether, with a plug on the end. The installer will
need to mount the holster and receptacle.
The holster is supplied with(3) 1/4-20 stainless steel self-tapping screws. Make sure the material beneath the bracket is substantial and
thick enough to hold self-tapping screws. Make sure the area on the back side of the mounting surface is clear of obstructions. We
recommend a minimum thickness of 3/32" (.093" - 2.4 mm) in aluminum and 5/64 (.078"-2mm) in steel See the chart in Figure 5.2.1 to
determine the correct pilot hole size.
TIGHTEN DOME NUT
TO 37 IN-LBS (4.2 N-M)
STRIP 1/4" (6mm)
OF INSULATION
REMOVE 6" (150mm) OF
JACKET AND TEFLON TAPE
1/8" (3mm) OF CABLE JACKET
PAST FITTING
NOTE:
CABLE IS GEL FILLED TO PREVENT MOISTURE WICKING
INTO ENCLOSURE. GEL IS NON-HAZARDOUS AND
SHOULD BE WIPED OFF CONDUCTORS WITH RAG.