4.5 ELEVATION TRAVEL STOPS
The range of elevation travel for the Monsoon Monitor is 90 degrees above zero to 45 degrees below zero. The elevation range may be
limited by installing the supplied stop bolts at the locations shown is figures 4.5A and 4.5B. Consult factory for other ranges. The figures
include installation notes.
Fig 4.5A
Elevation Travel Limits
Fig 4.5B
Elevation Travel Stop Locations
Pry out plastic plug and install Stop Bolt
to obtain desired travel limits.
Elevation travel with no Stop Bolts is
90° above and 45° below zero.
4.6 PRESSURE GAGE PORT
There is a ¼” NPT female threaded hole on the back of the monitor. The hole is plugged from the factory. If a pressure gage is desired,
unscrew the plug and install the gage using pipe sealant. Make sure the gage does not interfere with the elevation handwheel.
4.7 DRAIN
There is no drain on the Monsoon Monitor itself. A drain valve should be installed on the monitor's inlet piping.
14
PLASTIC
PLUG
#VM4124
A
30° ABOVE
HORIZONTAL
B
45° ABOVE
HORIZONTAL
STOP BOLT
#Y4145
C
30° BELOW
HORIZONTAL