![TAS PowerTek TPF-56 User Manual Download Page 50](http://html1.mh-extra.com/html/tas-powertek/tpf-56/tpf-56_user-manual_3630179050.webp)
PARAMETER
MIN
MAX
STEP
SIZE
FACTORY
Settings
Communication
1] Panel ID
00000000
99999999
1
00000001
2] ErasData 4 New ID
(Yes/ No)
No
Yes
-
No
3] Baud Rate – COM1
4800
9600
19200
57600
4800
57600
1
57600
4] Set Time
(HH/MM/SS) 24Hrs clock
_
_
_
Current Time
5] Set Date
(DD/MM/YY)
_
_
_
Current Date
6] Initialize RTC
(Yes/No)
_
_
_
No
7] Clear Battery fault
(Yes/ No)
_
_
_
No
8] Select Log Time: 60 MIN
30 MIN
15 MIN
10 MIN
60 MIN
10 MIN
1
60 MIN
9] Erasedata 4LOGTIME
(Yes/ No)
No
Yes
-
No
10] OvrWrt INTER LOG
(Yes/ No)
No
Yes
-
No
11] OvrWrt EVENT LOG
((Yes/ No)
No
Yes
-
Yes
12] COM 2 Function :None
Modbus ASCII
Modbus RTU
GSM
NONE
GSM
-
Mod-bus RTU
13] Baud Rate – COM 2
4800
/
9600
4800
9600
1
9600
14] Service Provider
000000000
9999999999
1
0000000000
15] SMS Receiver No
0000000000
9999999999
1
0000000000
Intelligent Power Factor Controller TPF-56
Factory Default Settings
50 of 56
Version 1.1.5 22
nd
March, 2016