Rated Supply voltage :User can set rated supply voltage of
panel.
Ext-PT ratio: In case the external PT is used, this ratio can
be set.
Cur CT Primary: Rated Feedback Load current for mains.
NOTE: PT ratio and CT Ratio are adjusted such that Panel
VA Rating Should not Exceed 50 MVA.
DT Ratio: Set the distribution transformer ratio.
Power Factor Limits: PF limits can be set as inductive or
capacitive. Also Target PF band can be set as Upper PF and
Lower PF limit. These limits can be set for Mains & or for
Generator.
Password: Enable or disable password.
Change Password: Set new value of password (4 digit).
Factory default password is “0000”.
Load Default: Loads factory set default parameters.
THD to Display: Type of THD to be displayed for V and I. R-
THD (RMS), F-THD (fundamental).
Reset Energy Counter: Reset all energy counters to zero.
AUX OP1 FUNCTION :Program the auxiliary output to
become NC due to any of the following :None, TripFlt,
Sys Flt, OutOfBank.
AUX IP1 FUNCTION : Set an action through auxiliary input
None ,O/P En Di (output enable disable) , Mains/generator,
Reset Bank Flt. When controller is on Mains mode then on
main screen shows (arrow). And if controller is on
generator mode then on main screen shows (arrow).
General & I/O
continued..
System
Intelligent Power Factor Controller TPF-56
31 of 56
Version 1.1.5 22
nd
March, 2016
CUR CT Primary
: 1000
PF Up Lim: Mains
[Cap : 0 ] 0.999
PF Up Lim: Mains
Cap: 0 [0.999]
PF Low Lim: Mains
[Ind : 1] 0.990
PF Low Lim: Mains
Ind : 1 [0.999]
Password
Disable :
Change Password
: 0000
Load Default
No :
THD To Display
F-THD :
Reset energy Cnt
No :
AUX OP1 FUNCTION
None :
AUX IP1 FUNCTION
None :
EXT-PT Ratio
0001.0 : 1
Rated Supply Vtg
(L-N) : 0254.0 V
DT Ratio
0001.0 : 1
PF Up Lim: Gen
[Cap : 0 ] 0.820
PF Up Lim: Gen
Cap: 0 [0.820]
PF Low Lim: Gen
[Cap : 0] 0.800
PF Low Lim: Gen
Cap : 0 [0.800]