PARAMETER
MIN
MAX
STEP SIZE
FACTORY DEFAULT
GENERAL I/O
Password (Enable/
Disable)
Enable
Disable
-
Disable
Change password
0000
9999
1
0000
Load default (Yes/ No)
No
Yes
-
No
THD to display (F–THD/ R-
THD)
F-THD
R- THD
-
F-THD
Reset energy counter
(Yes/No)
No
Yes
-
NO
Aux OP1 FUNCTION
(None / TripFlt / Sys Flt/
Out Of Bank.
None
Out Of Bank
-
None
Aux IP1 FUNCTION
(None / O/P En Di/Mains
/Gen/ Reset Bnk Flt.
None
Reset Bnk Flt
-
None
Factory Default Settings
Intelligent Power Factor Controller TPF-56
47 of 56
Version 1.1.5 22
nd
March, 2016
PARAMETER
MIN
MAX
STEP SIZE
FACTORY DEFAULT
SYSTEM
Rated Supply Vtg.
(L-N)
60
290
1
254
EXT-PT Ratio
1
299.9
1
1
Current CT Primary (Amp)
(only in user editable
steps option)
1
8000
1
1000
NOTE: PT ratio and CT Ratio are adjusted such that Panel VA Rating Should not Exceed 50 MVA.
DT Ratio
1
299.9
1
1
PF Upper limit: Mains
0.700
0.999
1
CAP 0.999
PF Lower limit: Mains
0.700
0.999
1
IND 0.990
PF Upper limit: Gen
0.700
0.999
1
CAP 0.820
PF Lower limit: Gen
0.700
0.999
1
CAP 0.800