![TAS PowerTek TPF-56 User Manual Download Page 19](http://html1.mh-extra.com/html/tas-powertek/tpf-56/tpf-56_user-manual_3630179019.webp)
Front fascia
–
LCD screen
First
line of display indicates the PF value, inductive / capacitive PF,
mode of operation and fault /OK status:
“PF
= 1.000” indicates the overall PF of the system.
“+” or “-” indicates if this PF is inductive or capacitive respectively.
“A” or “M” indicates the Auto and Manual mode of operation respectively.
“ ” or “ ” indicates the Mains and Generator mode of operation respectively.
“OK” (blinking) indicates status of the system, healthy or faulty.
Last two characters represent one of the following status:
Second
line indicates the status of each capacitor bank by symbols.
‘I AM OK’ Blinking LED indicates the controller’s health status ,i.e. the
controller is working okay. If this LED stays continuously ON or
continuously OFF, then, it means the Controller is not functioning properly.
OK
Controller status is OK
ZV
Zero voltage
OV
Over voltage
UV
Under voltage
VH
Voltage over-harmonics THD%
IH
Current over-harmonics THD%
BF
Battery Fail for Battery or RTC faulty
ZC
Zero current in any one phase
Intelligent Power Factor Controller TPF-56
AS
Auto-Synchronization Pending
19 of 56
Version 1.1.5 22
nd
March, 2016
- I am OK (Blinking Green colour LED) to indicate the
healthy state of Controller.
OB
Out of Banks (Insufficient Total
Capacitive kVAr – Warning.
OT
Over Temperature
UF
Under Frequency
OF
Over Frequency
UL
Under Load
BL
Low Battery Warning
OC
System Over Current Warning
PF=+1.000 A OK