Solo Plus Instructions 1-800-782-9927 Version 12-13
Tarm Biomass · 4 Britton Lane · Lyme, NH 03768
3.4 Connections to the Boiler
The following connections must be made to the boiler, in order for it to function:
The boiler flue gas exhaust collar must be connected to the chimney system.
The heating system piping must be connected to the boiler supply and return connections.
Electrical power must be provided at the boiler electrical terminal box.
3.4.1 Chimney Connection
The connection between the boiler and the chimney system should be single wall 24 gauge (minimum)
stainless or black pipe, unless prohibited by the local code authority.
The single wall chimney connector must not pass through an attic, roof space, closet or similar
concealed space, or a floor, or ceiling.
Where passage through a wall or partition of combustible construction is desired, the installa-
tion must conform to NFPA 211 or to Canadian CAN/CSA B365
The chimney connection pipe must be placed over the outside of the boiler’s flue gas exhaust
pipe
(Fig. 3.3).
A boiler flue with an internal dimension of 5.8‖ (149 mm) is used – see speci-
fication data in
Section 6.3
.
The chimney connector sections must be attached to the boiler and to each other with the
crimped (male) end pointing towards the boiler. All joints, including the connection at the
boiler collar, must be secured with three sheet metal screws.
A barometric regulator (draft damper), if used, should be incorporated into the connector
(Refer to
Section 3.2
for more information).
Boiler Installation & Start-up > Connections to the Boiler
Page 20
CAUTION
CAUTION
☼
☼
☼
☼
Do not install a flue damper in the exhaust venting system of this unit.
Do not connect this unit to a chimney flue serving another heating appliance, unless approved by
the local code authority.
Do not connect the boiler to any air distribution duct or system.
Install vent at clearances specified by the vent manufacturer.
Fig. 3.3 Flue Outlet with collar (SP 40 shown)