19.
Connect the backup batteries. The batteries connect to the power supply board
by inserting the connector onto the header pins located on the bottom right of
the power supply board which the 115-230 VAC 50-60Hz power supply was
connected. Although the pin is polarized, ensure correct polarity when
connecting the backup batteries. Red-positive & Black-negative.
WARNING:
The order in which 115-230 VAC 50-60Hz or backup
batteries is connected does not matter. However, once either the
batteries are connected OR the 115-230 VAC 50-60Hz line is
energized,
THE UNIT WILL BECOME “HOT” ENERGIZED.
It is the installer’s obligation to ensure compliance with all national,
regional, and local regulations
Programming Instructions
To program the AOR-8 or AOR-16 Command unit, each bank of eight (8)
Talkaphone Area of Rescue emergency analog phones must have their own
internal consolidator programmed. To program each internal consolidator, call it by
either dialing the phone numb
er of the line connected to that bank’s Telco “IN” port
or by lifting the selecting the appropriate line of the built in handset. In either case,
the consolidator will respond with three beeps. Each consolidator will respond to all
programming requests in one of two ways:
1 Beep
Command completed successfully
2 Beeps
Error(s) detected
If you hear two beeps, enter the code again. If you hear two beeps a second time,
hang up and try again.
Remote Mode
In Remote Mode, if a standard telephone company phone line is being utilized via
the Telco
“IN” connection, the consolidator does not need to be programmed.
Move on to Programming the Talkaphone Area of Rescue Emergency Analog
Phones.
If a PBX line is being connected to the Telco
“IN” port, the consolidator must be
programmed for PBX mode:
1.
Call the consolidator (listen for 3 beeps)
2.
Enter Guard Access Code: *31**
3.
Program the Consolidator for a PBX line: *39*2*
Summary of Contents for AOR-8