Fire Routing O/P
The Fire Routing O/P connection provides voltage free connections on terminals ( + ), ( - ) and ( E ) of the
horizontal terminal-strip Y-1. Connect the screen of the Fire Routing I/O cabling to the E terminal of the Fire
Routing O/P connection. The screen of the Fire Routing I/O cabling is the cabling earth connection.
Connect only compatible devices to this monitored output. The Fire Routing output is monitored for open
and short-circuit fault conditions when using a 10K End Of Line Resistor (EOLR). The Fire Routing output is
protected by 500mA self-resetting-fuse. Connect only polarized circuits to this voltage reversing output.
A suppression diode must be fitted to the Fire Routing O/P circuit when the circuit includes a relay. The sup-
pression diode suppresses interference generated by the relay when it operates.
Reference Appendix A, Specifications for cabling type, length and load for this output connection.
Configure this output using the touch screen menu of the Taktis Fire Control Panel. Set configurations in the
touch screen menu to operate and monitor devices connected to this output.
The figure below illustrates an example of a Fire Routing output containing a relay circuit:
Figure 3-33
Fire Routing and Fault Routing
Programmable Inputs
Programmable Inputs (PROG I/P) of the Taktis Fire Control Panel contain three programmable inputs and one
0 volt terminal. The programmable inputs are non-monitored and are activated by voltage free contacts.
Connect the 0V terminal to the Prog I/P terminal in the circuit to activate the programmable function.
All inputs are non-latching as a default condition of the fire control panel. The line impedance of the circuit
connection to the Prog I/P terminals must be less than 50 ohms. The three programmable inputs can be
configured to provide separate actions, delays, zones and location messaging using the menu of the touch
panel display.
),5(
5287,1*
23
.
(2/5
5HOD\
3RODUL]LQJ
'LRGH
6XSSUHVVLRQ
'LRGH
(
Summary of Contents for Incite Fire S3
Page 1: ...Taktis Operating Instructions Part Number OPIN 000004IN Revision E01 02 Date 18 09 2015...
Page 2: ......
Page 3: ......
Page 4: ...D F C B A E...
Page 5: ...I G H J...
Page 6: ......
Page 7: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 12: ......
Page 13: ......
Page 14: ......
Page 15: ......
Page 16: ......
Page 17: ......
Page 19: ......
Page 20: ......
Page 21: ......
Page 22: ......
Page 23: ......
Page 24: ......
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ......
Page 29: ......
Page 30: ......
Page 31: ......
Page 32: ......
Page 33: ......
Page 34: ......
Page 35: ......
Page 36: ......
Page 37: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......
Page 48: ......
Page 49: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......
Page 60: ......
Page 61: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ...Part Number OPIN 000004IN Revision E01 02 Date 18 09 2015...
Page 211: ......