FY operation manual 48
Parameter
Parameter
Symbol
Content
Range
Default
Level
Hide/
Display
MAX
MIN
PV2
Valve opening monitor
100.0
0.0
---
Fast
OUTY=2
&
SET7.1
OUTY
Hardware drive selection
0 : single output control
1 : dual output control
2 : valve control with feedback
3 : valve control without feedback
selection
4 : single phase control
4
0
0
Level 4
---
INP2
Sub input type selection
0 : none
1 : 10~50mV / 4~20mA / 1~5V /
2~10V
(only available in remote SV)
2 : 0~50mV / 0~20mA / 0~5V /
0~10V
(only available in remote SV)
3 : valve feedback
4 : CT input
4
0
0
Level 4
---
PMAC
Automatic valve position adjustment
0 : OFF stop automatic adjust
1 : ON start automatic adjust
2 : E_PB Valve position determined
by external button
E_PB
OFF
OFF
Fast
OUTY=2
RUCY
Motor valve traveling time
Time unit
:
second
150
5
5
Fast
OUTY =
2 or 3
CYT1
Motor valve action interval time.
Time unit : second
10
1
5
Fast
OUTY =
2 or 3
HYSM
Motor valve action main adjustment
unit : percentage
5.0
0.0
1.0
Fast
OUTY =
2 or 3
HYS1
Motor valve action sub adjustment
unit : percentage
HYSM
0
0.5
Fast
OUTY =
2 or 3
Motor valve Initial Setting
Set Motor valve traveling
time
( RUCY )
Set motor valve action
interval time
( CYT1 )
Set motor valve action
main hysteresis
( HYSM )
Set motor valve action
sub hysteresis
( HYS1 )
Without feedback
resistance
Executing automatic valve
position adjustment
( PMAC = ON )
Set motor valve action
interval time
( CYT1 )
Set motor valve action
main hysteresis
( HYSM )
Set motor valve action
sub hysteresis
( HYS1 )
With feedback
resistance
1. Executing automatic valve position adjustment
Parameter
Symbol
Content
Default
Level
PMAC
Automatic valve position adjustment
0 : OFF stop automatic adjust
1 : ON start automatic adjust
2 : E_PB Valve position determined
by external button
OFF
Fast
The motor valve low position(ANL2) and high position(ANH2) are calibrated and the travel time from completely open
to completely closed is set automatically
When the measurement has been complete the setting of the parameter will change to OFF.”PMER” will be display if any
of following errors occurs during execution.If an error occur check the wiring and other factors and execute automatic valve