FY operation manual 72
15.2 Input modify to RTD
Jumper Position
Software Setting
Plug 2 pcs of Jumper in the left slot as shown
Parameter set as“INP1=PT1~PT3”
SET 2_2 = 1
TRCL = 0
TRCH = 5FFF
INP1 = PT1
USPL = 850.0
LSPL = -199.9
Adjusts "TRCL" until PV = -199.9
Input PT100 signal -199.9°C
Adjusts "TRCH" until PV = 850.0
Input -199.9°C Check the PV = -199.9
Input 850.0°C Check the PV = 850.0
OK ?
to display TRCL & TRCH
YES
NO
Step A
Step B
Step C
Step D
Step E
Repeat step A~E 3~4 times
YES
NO
OK ?
RTD calibration flowchart
Start
End
Set the range you want
Ex: Low = 0.0 , High = 200.0
Set LSPL = 0.0 , USPL = 200.0
Input PT100 signal 850.0°C
Notes
When input is thermocouple or PT100, it has been calibrated and tested at the
factory, we don’t recommend customers to make
Their own calibration.