FY operation manual 42
11.3 Remote SV
Description
Remote SV functions as an analog signal (4~20mA or 0~10V) generated by external devices (EX: PLC AO module, transmitter)
to the Remote SV terminal of the controller, to change the SV with a preset range.
Remote SV signal selection: 4~20mA, 0~20mA, 0~5V, 0~10V, 1~5V, 2~10V
Function Diagram
C o n t r o l
o u t p u t
P o w e r
E l e c t r i c
f u r n a c e
S e n s o r i n p u t
P L C A O
m o d u l e
/ transmitter
Remote SV input
20.00
mA
SSR
-
+
PV
SV
OUT1
%
0
20
40
60
80
100
100.0
SET A/M
TAIE
FY900
OUT1
OUT2
AT
AL1
AL2
AL3
MAN
PRO
50.0
Parameter
Parameter
Symbol
Content
Range
Default
Level
Hide/
Display
MAX
MIN
SET0.3
0 : Remote SV disable
1 : Remote SV enable
1
0
0
Level 4
---
INP2
Sub input type selection
0 : none
1 : 10~50mV / 4~20mA / 1~5V /
2~10V
(only available in remote SV)
2 : 0~50mV / 0~20mA / 0~5V /
0~10V
(only available in remote SV)
3 : valve feedback
4 : CT input
4
0
0
Level 4
---
ANL2
Sub input zero calibration
9999
-1999
0
Level 3
SET2.4
ANH2
Sub input span calibration
(hex display)
0x7FFF
0x0000
0x5FFF
Level 3
SET2.4
Examples
Input signal is K1 and its range is -50.0~600.0. When an external analog signal is input to the Remote SV
terminal, the signal will be based on the range presents linear display of SV parameters
When the signal input value is less than 2.4mA, the PV position shows nnn2, indicating that the signal of Remote SV is lower than
the lower limit value
When the signal input value is greater than 21.6mA, the PV position shows uuu2, indicating that the signal of Remote SV is higher
than the upper limit value
Remote SV
4.0
20.0
mA
2.4 (-10%)
21.6 (110%)
Remote SV lower limit -10%
Remote SV lower limit
Remote SV upperer limit +10%
Remote SV upper limit
Parameter setting
Level
Parameter
Set value
Description
4
SET0.3
1
Enable Remote SV function
4
INP2
1
Remote SV signal=4~20mA
3
ANL2
744
Remote SV signal low point calibration value
(each controller calibrate value is different)
3
ANH2
0x657C
Remote SV signal high point calibration value
(each controller calibrate value is different)
Summary of Contents for FY400
Page 85: ...FY operation manual 84 MEMO...
Page 86: ...85 FY operation manual MEMO...
Page 87: ...FY operation manual 86 MEMO...
Page 88: ...87 FY operation manual MEMO...