Appendix 1 list of Parameters
State 16.11.15
Misprints and technical changes reserved
Page 15
13: Command/Status Words
ID
Name
Value-Range
Default-Value
Unit
Access
550 DrvCtrl Act
0000h ... FFFFh
0000h
[bits]
R
Actual status of control word 1
Control word 1 can be controlled by four different sources (field bus, digital inputs, PG4000 or U-drive
Manager)!
The bits for the four control words (Par.551 to 554) are incorporated in Control Word 1 or linked
(1=dominant).
Bit Name
Notes
0 Reset
Only possible when the drive is
not
started!
1 Running
Start the drive.
2 Direction CCW
Motor
turning counter-clockwise
3 Hold
Drive braking with current limit after rotational speed of Nil
4 Preset Speed 1
Fixed speeds 3, 5, 6 and 7 are controlled using binary code from the bit
combinations in Bits 4-6. Example: fixed speed 5 = Bit 4 (fixed speed 1) + Bit
6 (fixed speed 4)
See also Par.110-116 and 565
5 Preset Speed 2
6 Preset Speed 4
7 Ramp 1
Ramps 3, 5, 6 and 7 are controlled using binary codes from the bit
combinations in Bits 7-9. Example: ramp 3 = Bit 7 (ramp 1) + Bit 8 (ramp 2)
If no bit is triggered then ramp 0 is active!
See also Par.566 und parameter group 6
8 Ramp 2
9 Ramp 4
10 Slave Function
Incremental setpoint
11 Change Slave direction
Invert direction of rotation for Slave operation
12 SetDisableController
e.g.: for repair switch function
13 Digital Motorpoti
Switch on motor potentiometer
14 Motorpoti Up
15 Motorpoti Down
13: Command/Status Words
ID
Name
Value-Range
Default-Value
Unit
Access
551 DrvCtrl FBus
0000h ... FFFFh
0000h
[bits]
R
552 DrvCtrl D-In
0000h ... FFFFh
0000h
[bits]
R
553 DrvCtrl Kpd/PC
0000h ... FFFFh
0000h
[bits]
RW
554 DrvCtrl Command
0000h ... FFFFh
0000h
[bits]
RW