![Tadiran Telecom AVL-200 Service Manual Download Page 28](http://html1.mh-extra.com/html/tadiran-telecom/avl-200/avl-200_service-manual_3238916028.webp)
SKY
-
28
-
General Troubleshooting (continued).
Symptom
Probable Cause
Corrective Action
4
In Cool mode: high
pressure, or;
In Heat mode:
outdoor
coil freeze.
1. Winding of outdoor fan
motor is shorted.
1. Replace outdoor fan motor.
5
Only indoor fan
motor and outdoor
fan motor are
working. No
cooling and/or
heating take place.
1. Overload safety device on
compressor is cut out due
to high temperature.
2. Compressor
winding
shorted.
3. Pressure is too high.
1. Switch Off power and try again after
one hour.
2.
Replace
compressor.
3.
Check HP controller. Press RESET
button.
6
No air supply at
indoor unit
(compressor
operates).
1. Indoor fan motor is blocked
or turns slowly.
2. Loose or broken V-belt.
3. Indoor fan motor winding is
burnt.
4. In Heat mode: delayed
start for indoor fan motor.
5. Clogged
air
filters.
1. Check voltage. Repair wiring if
necessary. Check indoor fan wheel if
tight on motor shaft. Tighten if
necessary.
2. Tighten or replace V-belt.
3. Replace indoor fan motor.
4. Normal software delay (max. 20 sec.).
5. Clean
filters.
7
Low Capacity.
1. Lack of refrigerant (will be
accompanied by whistling
noise); causes ice
formation on the
evaporator coil (in Cool
mode).
2. Clogged
air
filters.
1. Unit must be charged (according to
the nameplate) after localizing the gas
leak.
2. Clean
filters.
8
In Heat mode: only
compressor runs,
outdoor and indoor
fan motors are
stopped.
A/C operates in De-Icing cycle. Wait (max.) 10 min. until the A/C resumes
to normal operation.
Summary of Contents for AVL-200
Page 9: ...SKY 9 4 Refrigeration Cycle...
Page 12: ...SKY 12 6 Electrical Wiring Diagram...
Page 13: ...SKY 13...
Page 14: ...SKY 14 NOTES...
Page 22: ...SKY 22 NOTES...
Page 32: ...SKY 32 NOTES...
Page 35: ......
Page 36: ...EN POWER SKY AVL AVR 200 300 V01 R01 JUN 2005...