0-003-2063-2 (EN)

8 (8)

ACTUATOR INSTALLATION

The switches on the circuit board
should be set before the actuator is
installed. There are no other switches
or potentiometers that should be set or
adjusted.

To make an end position adjustment,
you only have to switch the switch
»OP/ADJ« into its ADJ position, when
the supply voltage has been turned on,
and then back to its OP position.

When an end position adjustment is
made, Forta closes the valve and opens
it fully.  The adjustment is finished by
the actuator closing the valve again; the
electronic circuitry then adjusts the
stroke and the running time to the
valve.  The set values are stored in the
EEPROM of the actuator so that they
will remain after a loss of voltage.

When the end position adjustment is
complete, the actuator starts to control
the valve according to the control
signal.

MAINTENANCE

The actuator is maintenance-free.

ACCESSORIES

Circuit Board M800 Spare .................................................................... 1-001-0674-0

TAC Forta Handbook (GB) ...................................................................... 0-004-7804

S2-Forta ............................................................................................... 880-0104-000

STS-Forta M310/M800 ........................................................................ 880-0107-010

NiCd batteries for the STS .................................................................... 1-001-9024-0

TAC AB, Jägershillgatan 18, SE-213 75  MALMÖ, SWEDEN, +46 40 38 68 50 (switchboard), tac.com

Summary of Contents for Forta M800

Page 1: ...next page Supply voltage 24 V AC 10 40 50 60 Hz Power consumption average 15 VA Transformer sizing 50 VA Running time Modulating 10 25 mm 0 39 1 in 15 s Modulating 25 32 mm 1 1 26 in 20 s Modulating 1...

Page 2: ...rease decrease signal or by a variable direct voltage If an increase decrease signal is used the actuator normally moves inwards on an increase signal and outwards on a decrease signal see Settings Ma...

Page 3: ...over it is charged continuously for maintenance purposes Batteries for the STS uses NiCd SELF TESTING SAFETY DEVICE STS Figure 4 TECHNICAL DATA STS Supply voltage G 24 V AC 10 G0 return Output voltage...

Page 4: ...accepted in simplified installations on the following conditions the cables between the controller and actuator are shorter than 100 m 328 ft the cross sectional area is larger than 1 5 mm2 AWG 16 an...

Page 5: ...a Controller Normal installation 4 wires to the actuator Short cable installation 3 wires to the actuator Forta Controller Forta Controller Normal installation 5 wires to the actuator Short cable inst...

Page 6: ...AC supply to the controller TAC 239W TAC 6711 TAC Xenta TAC 8000 TAC 230U TAC 2000 TAC 9000 TAC 77xx Modulating control 16 V DC supply to the controller TAC 218E RM TAC 221L TAC 228R RL RF TAC 239W T...

Page 7: ...OFF position as the switch MOD INC is not valid during sequence or parallel control 4 Voltage range 0 10 2 10 You can choose whether to use the control signal voltage range 0 10 V or 2 10 V 5 Part of...

Page 8: ...ent is finished by the actuator closing the valve again the electronic circuitry then adjusts the stroke and the running time to the valve The set values are stored in the EEPROM of the actuator so th...