The actuator may be mounted
horizontally, vertically and in any
position in between, but 

not

 upside

down, see figure 3.

N.B.!

 Do not use the actuator for the

DN15 valves V298, V282, V294, V384,
V386 and V394.

To mount the actuator on a valve, slide
the actuator onto the valve neck, thus
making the square nut on the valve
spindle fit into the groove on the cross
bar. Then slide the brace into the
groove on the valve neck and secure
the nuts.

Figure 3

MOUNTING

STS is a processor controlled, battery
operated safety device which monitors
the presence of supply voltage to Forta
actuators.  The device supplies the
actuator with power so that the actuator
is able to close the valve in the event of
a loss of power.

The battery is tested periodically during
normal operation.  Moreover, it is
charged  continuously for maintenance
purposes.

Batteries for the STS uses NiCd.

SELF TESTING SAFETY DEVICE, STS

Figure 4

TECHNICAL DATA, STS

Supply voltage, G ........................................ 24 V AC ±10 %

G0 ........................................................................... return

Output voltage AC-DC, GF .......................... 24 V DC ±10 %

G0F ......................................... return, alt. 24 V AC ±10 %

Time to toggle AC to DC ......................................... max. 5 s
DC voltage supplied during .......................................... 70  s
Inputs:

Battery A ..................................... 8,4 V DC–min 600 mAh

Outputs:

Battery B, “rapid charging” ................................... 115 mA
Alarm outputs KC, K1 and K2

............................................ 2 A–24 V AC two-way SPDT

Indication:

Green LED ............................................ Normal operation
Red LED .................................................................. Alarm
Red LED on circuit board ........... Rapid charging is active

Settings:

Bypass MAN ............................ no jumper, external button
Bypass AUTO ........................ jumper on, internal function

Ambient temperature ......... –10 °C – +50 °C (14°F - 122°F)
Ambient humidity ............................................ max 65 % RH
Enclosure rating ........................................................... IP 44
Standards:

Emission ............................................... EN 50081-1:1992
Immunity ............................................... EN 50082-1:1992
Heat ................................................................. IEC-68-2-2
Cold ................................................................. IEC-68-2-1

Materials:

Box ...................................................... PC Makrolon 8035
Lid ....................................................... PC Makrolon 8035
Bracket ............................................................. SS 1412-2

Color ............................................................................ black
Weight, including battery ............................... 0.3 kg (0.7 lb.)
Dimensions .............. please refer to the dimension drawing

Summary of Contents for Forta M800

Page 1: ...next page Supply voltage 24 V AC 10 40 50 60 Hz Power consumption average 15 VA Transformer sizing 50 VA Running time Modulating 10 25 mm 0 39 1 in 15 s Modulating 25 32 mm 1 1 26 in 20 s Modulating 1...

Page 2: ...rease decrease signal or by a variable direct voltage If an increase decrease signal is used the actuator normally moves inwards on an increase signal and outwards on a decrease signal see Settings Ma...

Page 3: ...over it is charged continuously for maintenance purposes Batteries for the STS uses NiCd SELF TESTING SAFETY DEVICE STS Figure 4 TECHNICAL DATA STS Supply voltage G 24 V AC 10 G0 return Output voltage...

Page 4: ...accepted in simplified installations on the following conditions the cables between the controller and actuator are shorter than 100 m 328 ft the cross sectional area is larger than 1 5 mm2 AWG 16 an...

Page 5: ...a Controller Normal installation 4 wires to the actuator Short cable installation 3 wires to the actuator Forta Controller Forta Controller Normal installation 5 wires to the actuator Short cable inst...

Page 6: ...AC supply to the controller TAC 239W TAC 6711 TAC Xenta TAC 8000 TAC 230U TAC 2000 TAC 9000 TAC 77xx Modulating control 16 V DC supply to the controller TAC 218E RM TAC 221L TAC 228R RL RF TAC 239W T...

Page 7: ...OFF position as the switch MOD INC is not valid during sequence or parallel control 4 Voltage range 0 10 2 10 You can choose whether to use the control signal voltage range 0 10 V or 2 10 V 5 Part of...

Page 8: ...ent is finished by the actuator closing the valve again the electronic circuitry then adjusts the stroke and the running time to the valve The set values are stored in the EEPROM of the actuator so th...

Reviews: