background image

7 (8)

 0-003-2063-2 (EN)

SETTINGS

INC

0-5, 2-6

ADJ

LIN/LG

INV

300 s

2-10

5-10, 6-10

SEQ

OP

NORM

NORM

60 s

0-10

– – –

MOD

12

3

4

5

6

7

8

O

N

9

OUT

IN

Figure 8

Function in the

Description

“OFF” pos.

“ON” position

1

In

Out

Valve closing screw direction

2

Modulating

Increase/decrease

Control (not at Sequence)

3

Sequence

Sequence control

4

0-10 V

2-10 V

Voltage range

5

0-5 V, 2-6 V

5-10 V, 6-10 V

Part of voltage range

6

60 s

300 s

Running time

7

Normal

Inverted

Direction of movement

8

Normal

Linear/Logarithmic

Valve characteristic

9

Operation

End position adjust (mom.)Operation/End position adjustment

There are nine switches in a row on the
circuit board. On delivery (’Factory’), all
switches are in the “OFF” position.

1

Valve Closing Screw Direction—
IN / OUT

IN direction of movement is used when
the screw of the actuator moves
inwards to close the valve.

OUT direction of movement is used
when the screw of the actuator moves
outwards to close the valve.

Note! 

At power failure, the STS

closes according to this switch.
Y = 2 V at close valve.

2

Control signal—MOD / INC

TAC Forta can either be controlled by a
variable direct voltage, a so called
modulating signal (MOD), or by an
increase/decrease signal (INC).

3

Sequence or parallel control—
– – – / SEQ

With sequence (or parallel) control
(SEQ), two actuators/valves can be
controlled by only one control signal.

For each of these you can choose
which part of the voltage range to use,
the upper one, 5-10 V (6-10 V) or
the lower one, 0-5 V (2-6 V).

If the switch NORM / INV is in the
NORM position, the higher voltage
corresponds to 100% flow and the
lower one to 0%.

With NORM / INV in the INV position
you will get the opposite function.

Note!

 If sequence or parallel control

is 

not 

used, the switch – – – / SEQ

must be in the 

OFF position, as the

switch MOD / INC is not valid during
sequence or parallel control.

4

Voltage range—0-10 / 2-10

You can choose whether to use the
control signal voltage range 0-10 V or
2-10 V.

5

Part of voltage range—
0-5, 2-6 / 5-10. 6-10

You can choose which part of a voltage
range to use, the lower one 0-5 V
(2-6 V) or the upper one 5-10 V
(6-10 V).

If the switch is in the NORM position,
the higher voltage corresponds to 100%
flow and the lower one to 0%. To
achieve the opposite function, the
switch should be put in its INV position.

6

Running time—60 s / 300 s

With increase/decrease control, you can
choose a running time between 60 s or
300 s.

With modulating control, the running
time is always 15 s / 20 s / 30 s.

7

Direction of movement—
NORM / INV

When normal direction of movement is
used, the screw of the actuator moves
inwards when the control voltage
decreases or if the actuator gets a
decrease signal.

With the switch NORM / INV, the
direction of movement can be changed.

8

Linearization—NORM / LIN/LG

The motorized valve characteristics can
be modified. If you wish for the
characteristics to be affected, the
setting LIN/LG will make the
characteristics of an equally modified
percentage (EQM) valve almost linear.

On the other hand, with LIN/LG a
motorized valve equipped with a linear
valve will operate with ”Quick open
characteristics”. This means that with a
small control signal, the valve will be
almost completely open.

Note!

 For the actuator to register

new settings of the switches, the
supply voltage must be cut or the
manual operation handle lowered,
the settings done, and then the
handle raised again.

Please refer to illustration on page 2.

(This does not apply to the switch
OP/ADJ).

9

End position adjustment—
OP / ADJ

This switch is only used to adjust the
end positions when the actuator is
commissioned.

Momentarily put the switch in the ON
position. The actuator will automatically
find the end positions of the valve.

Summary of Contents for Forta M800

Page 1: ...next page Supply voltage 24 V AC 10 40 50 60 Hz Power consumption average 15 VA Transformer sizing 50 VA Running time Modulating 10 25 mm 0 39 1 in 15 s Modulating 25 32 mm 1 1 26 in 20 s Modulating 1...

Page 2: ...rease decrease signal or by a variable direct voltage If an increase decrease signal is used the actuator normally moves inwards on an increase signal and outwards on a decrease signal see Settings Ma...

Page 3: ...over it is charged continuously for maintenance purposes Batteries for the STS uses NiCd SELF TESTING SAFETY DEVICE STS Figure 4 TECHNICAL DATA STS Supply voltage G 24 V AC 10 G0 return Output voltage...

Page 4: ...accepted in simplified installations on the following conditions the cables between the controller and actuator are shorter than 100 m 328 ft the cross sectional area is larger than 1 5 mm2 AWG 16 an...

Page 5: ...a Controller Normal installation 4 wires to the actuator Short cable installation 3 wires to the actuator Forta Controller Forta Controller Normal installation 5 wires to the actuator Short cable inst...

Page 6: ...AC supply to the controller TAC 239W TAC 6711 TAC Xenta TAC 8000 TAC 230U TAC 2000 TAC 9000 TAC 77xx Modulating control 16 V DC supply to the controller TAC 218E RM TAC 221L TAC 228R RL RF TAC 239W T...

Page 7: ...OFF position as the switch MOD INC is not valid during sequence or parallel control 4 Voltage range 0 10 2 10 You can choose whether to use the control signal voltage range 0 10 V or 2 10 V 5 Part of...

Page 8: ...ent is finished by the actuator closing the valve again the electronic circuitry then adjusts the stroke and the running time to the valve The set values are stored in the EEPROM of the actuator so th...

Reviews: