Selector switch
42
Program selection (Progr.), assignment of priority (Vorr.)
Position of selector switch: Prog. / Vorr.
Pressing the yellow „
Eingabe
“ key for 2 seconds causes entry or exit
to/from the sub menu
normal (short) pressing switches from one position to the next
The value can be changed with the blue keys
ab/auf
(down/up).
ew
ex works = original setting by the factory
P16
– Actual used program : 16
Setting by pressing the blue keys
ab/auf
.
Pressing the yellow „
Eingabe
” key for 2 seconds causes entry to the
sub menu
Vorr.
(= priority)
A12
– Assignment of
second
priority to the output
A1
. I.e. the output
will be enabled, when all superior outputs with priority 1 are switched
off.
ew
= A10 (output
A1
switches independently)
A21
– Output
A2
has the highest priority 1.
ew
= A20 (output
A2
switches independently)
A31
– Output
A3
has the same (highest) priority 1 as
A2
.
ew
= A30 (output
A3
switches independently)
A40
– Output
A4
has assigned no priority. It can switch independently
from all other outputs.
ew
= A40 (output
A4
switches independently)
A12
– Pressing the yellow „
Eingabe
” key at the end of the menu, the
run starts again. Going back to normal operation happens by pressing
the yellow „
Eingabe
” key for 2 seconds, turning the selector switch or
automatically after one minute.
Vers:
In this switch position the software version of the computer is displayed (e.g. E5.2). It
shows the “intelligence” of the controller and must be advertised to the manufacturer
for enquiry calls. It cannot be changed.
Menü:
„Menü“ (= menu) allows the setting of about 50 different parameters, which are set ex
works to standard settings. Sometimes it is necessary to change them. A change of
these values should only be done, if the user has knowledge of all functions as these
settings can change the basic features of the controller. Different parameters are
stored in sub menus.