SYX66x Commissioning Guide
V1.10.3 300117
Page 39 of 61
The adaptive values are to be treated as a measurement of your building performance and so adaption should be
enabled. It should not be turned off without good reason and the customer informed as to why. Notes on why should
be left with the customer.
For more information on Optimiser performance and getting the best out of your control system please read.
“Optimising your control system” from SyxthSense. It is full of information on how to understand controllers and how
to fix issues perceived to be their making.
HWS Priority
– No Priority, On Pump, On Valve (See HWS Control)
Flow Eco Mode
– Enabled – Turns the heating off if the flow temp set point is very close to the room temp.
Optimiser Adapt
– Enabled – Allows the optimiser to self-learn the Warming Up and Cooling Down Rates. If disabled
the rates will be held at those settings provided in the Heating Control- Values list