SyxthSense Ltd
Copyright © 2021 SyxthSense Ltd. All rights reserved - 03/2021
PS
MOD3.102
- 19/29
Online store:
www.syxthsense.com
Enquiries: T:
0844 840 3100
E:
113
Digital Input Mode
Unsigned 16
0..8
0 = Disabled (no SRI effect)
1 = Close for ECO
2 = Open for ECO
3 = Close for OFF
4 = Open for OFF
5 = DI Contact Alarm
6 = Network
7 = Close for Night
114
Digital Input Delay
Unsigned 16
0..7200
0..7200 seconds (Default 0s)
115
Enable Lights Symbol
Unsigned 16
0..1
0 = Disabled (default)
1 = Enabled
116
Enable AC Symbol
Unsigned 16
0..1
0 = Disabled (default)
1 = Enabled
117
Lock Mode
Unsigned 16
0..3
0 = Lock mode disabled (default)
1 = On/Off/Boost workable only
2 = Temp settings only available
3 = All buttons disabled
118
Show Temperature Unit Selection Icon
Unsigned 16
0..1
0 = Disabled (default)
1 = Enabled
119
Built-In Sensor Calibration
Signed 16
-100..+100
-10.0..+10.0 °C/°F
120
RI1 Sensor Calibration
Signed 16
-100..+100
-10.0..+10.0 °C/°F
121
RI2 Sensor Calibration
Signed 16
-100..+100
-10.0..+10.0 °C/°F
122
Humidity Sensor Calibration
Signed 16
-100..+100
-10.0..+10.0 %rH
123
Humidity Display
Unsigned 16
0..1
0 = Disabled
1 = Enabled (default)
124
Override Mode Icon
Note: To release override set to None,
otherwise the user cannot set/unset.
Unsigned 16
0..4
0 = None (Default)
1= Auto
2 = Heating
3 = Cooling
4 = Ventilation
125
Party Mode (Boost) Time
Unsigned 16
0...480
0..480 minutes (Default 0)
0 = Disabled
126
Backlight Brightness
Unsigned 16
0..20
0..20 (default 5)
127
Relay Control Mode
Control = Controlled by the time schedule /
party mode boost
Network = Controlled by network.
Unsigned 16
0..1
0 = Control Normally Open
(Default)
1 = Control Normally Closed
2 = Network
128
Lock Mode Password
Unsigned 16
0..9999
0000...9999
129
Maintenance Mode Password
Unsigned 16
0..9999
0000...9999
130
Override A/C
Note: To release override set to None,
otherwise the user cannot set/unset.
Unsigned 16
0..2
0 = None (default)
1 = Override On
2 = Override Off
131
Override Lights
Note: To release override set to None,
otherwise the user cannot set/unset
Unsigned 16
0..2
0 = None (default)
1 = Override On
2 = Override Off
132
Override Lock Mode
Note: The parameter returns automatically to 0
allowing local control.
Unsigned 16
0..2
0 = None (default)
1 = Lock Screen
2 = Cancel Lock Mode
133
Enable OFF Icon
Unsigned 16
0..1
0 = Disabled (Default)
1 = Enabled (Home Screen)
134
Fan Speed Override (Advanced Mode)
Unsigned 16
1..8
1 = Register 135
2 = Speed 1
3 = Speed 2
4 = Speed 3
5 = Speed 4
6 = Speed 5
7 = Speed 6
8 = Register 111
135
Night Speed - Set Fan Speed in Night Mode
Unsigned 16
0..6
0..6
136
Relay Network Override (Overrides the relay
drive directly, local )
Unsigned 16
0..2
0 = No Override (Default)
1 = Override Relay On
2 = Override Relay Off
137
Staff Code
Unsigned 16
0..9999
0000...9999
Register
Parameter Description
Data Type
Raw Data
Range