With SRI-71 models the target setpoint can be sent to analogue 0-10Vdc outputs. The output value is 
scaled between Min. Setpoint  Adj. and Max. Setpoint Adj parameters. For example, if Min Setpoint = 
10 and Max. Setpoint = 30, and the current setpoint target is 22.5, the output will be 
((22.5-10.0)/(30.0-10.0))*100.0% = 62.5% (6.25V).

Centigrade to Fahrenheit 
Display

Target

65

.0

°F

Room

72

.8

°F

°F

°C

UNIT SELECTION

Target

18

.3

°C

Room

22

.7

°C

°F

°C

If Centigrade to Fahrenheit icon has been 
enabled (parameter System/Show Unit Swap) 
it is possible on the front screen to change 
the units by touching this icon.

This option is particularly useful in hospitality 
applications where the client base is 
expected to be international.

In addition (from Fw 4.01 onwards) at the 
commissioning it is possible to select default 
units from parameter System/Native Units. 
When changing the Native Units the device 
carries out Factory Default reload using the 
selected units (for all relevant settings). 

Warning: After changing the Native Units, 
the controller reloads defaults for ALL PARAMETERS.The Native Unit selection should be 
done at the start of the commissioning.

Further Settings and 
Information

The FURTHER SETTINGS shows additional user settings options on the SRI room interfaces:-

OFF icon to switch device to OFF (OFF icon is displayed here only if OFF icon has been enabled 
and the PARTY (BOOST) button has also been enabled) 

LOCK icon is used to lock the device. Number of different lock modes options exist.

CLEANING icon is used to enable timed cleaning mode.

CLOCK icon is used to set the time (SRI-P70 only).

CALENDAR icon is used to enter the programming screens to set the switching times, the tem-
perature targets (SRI-P70 only).

COG WHEEL icon allows entry to the maintenance mode. 

FURTHER SETTINGS AND INFORMATION

ACTIVATE FUNCTIONS 
BY SELECTING THE 
ICONS

LARGE CIRCLE 
CONTINUES TO 
DISPLAY THE SET 
COLOUR

USE ESC BUTTON TO 
SET  OR WAIT FOR A 
TIME-OUT

ENTRY SCREEN

TO ENABLE CLEANING MODE 
TOUCH THE ICON

SELECT COG WHEEL TO 
ENTER MAINTENANCE 
MODE (REQUIRES 
PASSWORD)

SELECT LOCK ICON TO 
LOCK THE THERMOSTAT 
FROM TAMPERING

SELECT CLEANING ICON 
TO ENABLE CLEANING 
MODE. THE DISPLAY 
WILL COUNT DOWN 
FROM 30 SECONDS
DURING WHICH ALL
BUTTONS ARE DISABLED
ALLOWING SCREEN
CLEANING. 

PRESS OFF BUTTON 
TO SWITCH THE
INTERFACE OFF

30

Clean Screen

MODIFY SWITCHING 
SCHEDULE (ONLY 
SRI-P70)

SET TIME AND DATE
(ONLY SRI-P70)

The FURTHER SETTINGS screen is protected by the Staff Code. As default the Staff Code is 
disabled (0000). If activated, the user will need to enter the 

Staff Code 

to enter the screen.

Fan Speed Display and  
Manual Override

The SRI70 series has fan icon and line bar to indicate the fan speed. It is also possible to use the line 
bar only to indicate other signals by disabling the fan icon.

Summary of Contents for SRI-70 Series

Page 1: ...SRI 70 3 x 0 10Vdc Outputs SRI 71 Digital Input for Overrides Measurement Product sheet MOD3 102 Type SRI 70 71 Model Type Model Description SRI 70 MOD 24 Modbus 3 5 Touchscreen User Interface Built...

Page 2: ...to 247 via Touchscreen Communication 9k6 19k2 38k4 57k6 76k8 Baud Parity None Even Odd 1 or 2 Stop Bits adjustable through Touchscreen BACnet BAC models Protocol BACnet MS TP Interface RS485 maximum...

Page 3: ...24V 24Vac dc Supply 0V 0V Supply Rin1 Remote NTC10 Temperature Sensor Input 1 Rin2 Remote NTC10 Temperature Sensor Input 2 Din Volt Free Digital Input Contact 485A Modbus BACnet MS TP RS485 A Connect...

Page 4: ...SPLAY SRI 70 WITH FAN SPEED 21 5 C Room 20 1 C A CONTROL MODE AUTO HEATING COOLING FAN VENTILATION FAN The SRI 70 room interface home screen has four touch sensitive areas that allow the system settin...

Page 5: ...xt parameter in the configuration pages By setting the description to Disabled the sensor reading is not displayed on the screen Note If all sensor displays are Disabled the ACTION CIRCLE displays the...

Page 6: ...onal user settings options on the SRI room interfaces OFF icon to switch device to OFF OFF icon is displayed here only if OFF icon has been enabled and the PARTY BOOST button has also been enabled LOC...

Page 7: ...2 Speed 0 Speed 1 Speed 2 Speed 0 Speed 3 A Auto SPEED SET BY NETWORK To set the fan speed or the line bar to a position touch the line bar fan icon area and the line icon and network variable is set...

Page 8: ...then the fan speed returns to speed 1 Operating Mode Icon The interface unit has Operating Mode icon that allows the unit operating mode to be set network variable 21 5 C Room 23 8 C CONTROL MODE PRE...

Page 9: ...on Not Visible default ENABLED OFF Icon is displayed in the HOME SCREEN in the FUNCTION BASED ICON area if the PARTY MODE has not been enabled Otherwise it is displayed in the FURTHER SET TINGS SCREEN...

Page 10: ...he front screen 21 5 C Room 20 1 C LIGHTS STATUS AND ON OFF SWITCH LIGHTS ON LIGHTS OFF A C STATUS AND ON OFF SWITCH A C ON A C OFF When touching the buttons the Lights and or AC Icon are either swith...

Page 11: ...rnal sensor 2 Res2 fault when activated not connected Built in sensor fault Digital Contact Fault Time Lost SRI P70 only Note If the sensor source has been set to Network then the alarm is inhibited E...

Page 12: ...levels can be scaled using the AO SP Min and AO SP MAX parameters Humidity Measurement RH option The models with RH option have a 2 rH accurate humidity sensor for room space humidity measurement The...

Page 13: ...home screen By clicking the icon it is possible to change the displayed language 18 5 C Room 22 7 C EN CLICK TO SET LANGUAGE ES CA BA FR IT PL EN FI SE DE NOTE If the Mode Icon has been activated the...

Page 14: ...Night 8 Disabled Digital Input Delay Digital Input Delay Timer transition from active to non active 0 7200 seconds Default 0s Internal Sensor Cal Internal Sensor One Point Compensation 10 0 10 0 C F R...

Page 15: ...meter Name Description Range Brightness Backlight Brightness 0 20 default 5 Enable Lights Enable Lights Icon Network Variable 0 Disabled default 1 Enabled Enable AC Enable AC Icon Network Variable 0 D...

Page 16: ...LAY Parameter Name Description Range SYSTEM Parameter Name Description Range Address Modbus Address Only Modbus versions BACnet MAC Address Only BACnet versions 0 247 Default 1 0 127 Default 1 Baud Ra...

Page 17: ...ister 101 needs to be entered Version Software Version x xx Modbus BACnet SYSTEM Parameter Name Description Range Register Parameter Description Data Type Raw Data Range FUNCTION CODE 01 READ COILS FU...

Page 18: ...rcentage 2 None 3 Temperature Rel Relative 4 State Select 102 Sensor 3 Source Unsigned 16 0 1 0 Buillt In Sensor Default 1 Network Sensor 103 Sensor 3 Network Temperature Signed 16 580 1220 58 0 122 0...

Page 19: ...Ventilation 125 Party Mode Boost Time Unsigned 16 0 480 0 480 minutes Default 0 0 Disabled 126 Backlight Brightness Unsigned 16 0 20 0 20 default 5 127 Relay Control Mode Control Controlled by the ti...

Page 20: ...ned 16 0 59 0 59 146 Current Day P version Unsigned 16 1 31 1 31 147 Current Month P version Unsigned 16 1 12 1 12 148 Current Year P version Unsigned 16 2015 2099 2015 2099 149 Current Hour Update Re...

Page 21: ...0 1 0 1 Default 0 216 Tuesday Switching Time 2 Target Unsigned 16 0 1 0 1 Default 0 217 Tuesday Switching Time 3 Target Unsigned 16 0 1 0 1 Default 0 218 Tuesday Switching Time 4 Target Unsigned 16 0...

Page 22: ...t Unsigned 16 0 1 0 1 Default 0 260 Sunday Switching Time 1 Unsigned 16 0 2400 0 2400 Default 0600 261 Sunday Switching Time 2 Unsigned 16 0 2400 0 2400 Default 1000 262 Sunday Switching Time 3 Unsign...

Page 23: ...xecute BIBB Object Number Of Instances Instance Assignments Device Object 1 Analog Input 6 AI 0 Sensor 3 Built In Sensor AI 1 Setpoint Calculated AI 2 Humidity Measurement AI 3 Sensor 1 RI1 AI 4 Senso...

Page 24: ...onfiguration parameters through the SRT touchscreen MutliState Value 7 MSV 0 Ring Colour Read Write 1 White 2 Red 3 Blue 4 Green 5 Orange 6 Yellow 7 Magnenta 8 Cyan 9 Sensor1 10 Sensor2 11 Sensor3 MSV...

Page 25: ...30 C 40107 Sensor 1 Source Unsigned 0 RI1 1 Network Sensor Default 40109 Fan Manual Control Mode Unsigned 0 Disabled default 1 1 Step 2 2 Step 3 3 Step 4 6 Step 5 1 Step Auto 6 2 Step Auto 7 3 Step Au...

Page 26: ...d 0 6 40137 Staff Code Unsigned 0000 9999 40138 Language Unsigned 0 English Default 1 Finnish 2 Swedish 3 French 4 Italian 5 Polish 6 Spanish 7 Catalan 8 Euskera 9 Gerrman 40139 Sensor 1 Text RI1 Netw...

Page 27: ...m Default 5000 40175 Analogue Output at Setpoint Minimum Unsigned 0 100 0 10 0V Default 0 40176 Analogue Output at Setpoint Maximum Unsigned 0 100 0 10 0V Default 100 40300 MAC ID Unsigned 0 127 Defau...

Page 28: ...SyxthSense Ltd Copyright 2021 SyxthSense Ltd All rights reserved 03 2021 PS MOD3 102 28 29 Online store www syxthsense com Enquiries T 0844 840 3100 E sales syxthsense com...

Page 29: ...SyxthSense Ltd Copyright 2021 SyxthSense Ltd All rights reserved 03 2021 PS MOD3 102 29 29 Online store www syxthsense com Enquiries T 0844 840 3100 E sales syxthsense com...

Reviews: