each day. A copy function is available to copy times and target temperatures from one day (or group)
to other day.
SETTING PROGRAM SCHEDULES
7 DAYS OR 5+2 DAYS
MODE SELECTION
7 Days
7 DAYS PROGRAMMING MODE
SELECT
DAY
Copy
Mon
Tue
Wed
Thu
Fri
Sat
Sun
0
12
24
18
6
Mon
Tue
Wed
Thu
Fri
Sat
Sun
Schedule Overview
VISUAL SCHEDULE
OVERVIEW
Time
Target
Monday
Set Values
TOUCH TIME TO
CHANGE
SWITCHING
TIME
TOUCH TARGET TO
SELECT SWITCH-
ING TARGET
7
4
1
.
0
8 9
5 6 -
2 3
Esc
Enter
Del
7
4
1
0
ENTER SELECTED PERIOD
SWITCHING TIME
:
Monday
Set Switching Time
07:40
0
12
24
18
6
Mon
On
Off
On
06:30
Off
13:00
On
18:00
Off
22:30
Off
23:30
Language Selection
The SRI-70 user pages can be displayed in
different languages by selecting the
language from the System Configuration
pages. By enabling the Show Language
Swap parameter the current language is
displayed at the bottom left corner of the
home screen. By clicking the icon it is
possible to change the displayed language.
18
.5
°C
Room
22
.7
°C
EN
CLICK TO SET LANGUAGE
ES
CA
BA
FR
IT
PL
EN
FI
SE
DE
NOTE: If the Mode Icon has been
activated, the Language Selection icon is
no longer available.
Configuration Parameters
Sensor 1 Source
Hardware
Input Settings
Sensor 2 Source
Network
Sensor 3 Source
Hardware
Digital Input Mode
Close for ECO
ENTER MAINTENANCE CODE FOR
MAINTENANCE MODE
CLICK TO ACCESS SETTINGS
GROUP
CLICK TO CHANGE
SETTING
ACCESS
MORE
SETTINGS
6666
8 9
5 6 -
2 3
Esc
OK
Del
Maintenance Code
Enter Code
7
4
1
0
Operating Modes
Parameter Groups
Display
Control Settings
Inputs
System
The SRI user interfaces are configured to operate in different modes via the configuration parameters
accessible through the maintenance mode.
To enter the maintenance mode click the COG WHEEL icon in the FURTHER SETTINGS SCREEN
and enter the maintenance mode password (default 6666).
Note:
The maintenance mode password can be changed in the configuration settings. Make sure that
you note the new password if changed.
CONTROL SETTINGS
Parameter Name
Description
Range
Nominal Setpoint
Nominal Setpoint
0.0...99.9°C/°F/% (Default 21.0°C)
Setpoint Limit Mode
Setpoint Limit Mode
0 = Absolute (Default)
1 = Relative