Lock Mode
After entering FURTHER INFORMATION screen, by selecting
the LOCK icon it is
0000
8 9
5 6 -
2 3
Esc
OK
Del
Lock Code
Enter Code
7
4
1
0
possible to lock the user interface. Now by
entering the LOCK CODE (default 0000), the SRI lock state can
be activated.
The lock mode can be configured to work in different ways:-
•
DISABLED: Lock Mode Icon Not Available
•
ADJUST ONLY: Allows Temporary Temperature Adjustment
Only
•
SCHEDULES ONLY: Allows adjustment of the Programmed
Times
•
NO INPUT: All Buttons Locked
Note: Current Lock status is retained after power cycle.
Alarm Display
When entering FURTHER
INFORMATION AND SETTINGS
screen and an alarm is active,
select the alarm icon for more
information.
FURTHER SETTINGS AND
INFORMATION
SELECT ALARM ICON FOR
MORE INFORMATION
Notifications
Internal Sensor Failure
External Sensor 1 Fault
External Sensor 2 Fault
Digital Contact Fault
Time Lost
The typical alarm reasons are:
•
External sensor 1 (Res1)
fault (when activated; not
connected)
•
External sensor 2 (Res2)
fault (when activated; not
connected)
•
Built-in sensor fault
•
Digital Contact Fault
•
Time Lost (SRI-P70 only)
Note:
If the sensor source has
been set to
Network
then the
alarm is inhibited.
External Sensor RI1 and RI2
Inputs
A remote NTC10k3 sensor can be connected to the RI1 and RI2 input and used for the monitoring
purposes. The measurement is always available over the communications network in MOD/BAC
models. If configured the reading is also showed on the display in the SMALL ACTION CIRCLE area.
With SRI-71 models the temperature readings can be sent to analogue Y1/Y2/Y3 0-10Vdc outputs.
DI1 Digital Volt-Free Input
The digital volt-free contact can be used to override the interface to ECO and OFF/FROST modes, or
for just monitoring purposed. The configuration options are:-
•
Close for ECO Mode
•
Open for ECO Mode
•
Close for OFF Mode
•
Open for OFF Mode
•
Alarm
•
Network
•
Close for Night
•
Disabled
"Close For" Configuration - The digital volt-free contact can be linked to e.g. external timer to switch
the user interface to OFF or ECO mode (input delay timer).
Lock Mode Options
Icon Active
Lock
Up and
Down/
FAN
PARTY
MODE /
OFF
ECO
AC
Lights
Programs
(SRI-P
Only)
Cleaning/
Clock
(SRI-P
Only)
DISABLED
NO
YES
YES
YES
YES
YES
YES
YES
ON/OFF ONLY
YES
NO
YES
NO
YES
YES
NO
YES
ADJUST ONLY
YES
YES
NO
NO
NO
NO
NO
YES
NO INPUT
YES
NO
NO
NO
NO
NO
NO
YES