SyxthSense Ltd
Copyright © 2021 SyxthSense Ltd. All rights reserved - 03/2021
PS
MOD3.102
- 23/29
Online store:
www.syxthsense.com
Enquiries: T:
0844 840 3100
E:
BACnet Standard Object
Types Supported
No dynamic Creation or Deletion supported. Objects, and object instances, are assigned to fixed
functions within the proprietary control application of the product as follows
WriteProperty
Yes
DS-WP-B
ReinitializeDevice
Yes
Who-Is
Yes
DM-DDB-B
I-Am
Yes
Who-Has
Yes
DM-DOB-B
I-Have
Yes
DeviceCommunicationControl
Yes
DM-DCC-B
TimeSynhronisation
Yes
DM-TS-B
Application Service
Initiate
Execute
BIBB
Object
Number Of
Instances
Instance Assignments
Device Object
1
Analog Input
6
AI(0) – Sensor 3 (Built-In Sensor)
AI(1) - Setpoint (Calculated)
AI(2) - Humidity Measurement
AI(3) – Sensor 1 (RI1)
AI(4) – Sensor 2 (RI2)
AI(5) – CO2 Measurement
Analogue Value
8
AV(0) - Nominal Setpoint
AV(1) - Sensor 1 Temp
AV(2) - Sensor 2 Temp
AV(3) - Sensor 3 Temp
AV(4) - Brightness
AV(5) - Y1 Output
AV(6) - Y2 Output
AV(7) - Y3 Output
Binary Input
5
BI(0) – Digital Input (DI1)
BI(1) – Boost (Party Mode) Status
BI(2) – Schedule Status (only SRI-P70)
BI(3) – Time Lost (only SRI-P70)
BI(4) – Auto Fan Status
Binary Output
11
BO(0) – Relay
BO(1) - OFF Status
*1
BO(2) - ECO Status
"1
BO(3) – Lights
*2
BO(4) – AC
*2
BO(5) – Lock
*1
BO(6) – Frost Icon
BO(7) - Non Volatile Update (updates
setpoints/configuration parameters)
BO(8) – Boost Icon
BO(9) – Reset Setpoint (User Adj)
*5
BO(10) – Night Status / Override