9.2 Connection diagram

GND

A GND

1

2

+Ub

MCTE03K1
05.10.2010

TCA 150D

Eingang

Input

10...24 V DC

(I

max

 

= 6 mA)

+

1

Ausgang

Output

0...10 V

(I

max

 

= 0.3 mA)

+

2

10...24 V DC

+

4

R

i

 

= 4 kΩ

0 1

0 = 

Setpoint 1

1 = 

Setpoint 2

q

TF..

TF

TF

KTY 81-210
PT 1000

3

+

-

1

Voltage supply 10...24 V DC

2

Output 0...10 V  

3

Temperature sensor KTY 81-210 or PT 1000

4

Voltage input for switch over Setpoint 1 / Setpoint 2

Operating Instructions 

TCA 150D

Enclosure

L-BAL-E119-GB 1318 Index 002

Part.-No. 00163357-GB

15/17

Summary of Contents for TCA 150D

Page 1: ...TCA 150D part no 32186 Control module for temperature Operating Instructions Software version D2033A from Version 1 00 L BAL E119 GB 1318 Index 002 Part No 00163357 GB english ...

Page 2: ...sioning 6 5 Electrical installation 7 5 1 Safety precautions 7 5 2 EMC compatible installation of control lines 7 5 3 Connection Voltage supply 7 5 4 Connection of sensor 7 5 5 Output voltage 0 10 V 8 5 6 Input for switch over Setpoint 1 Setpoint 2 8 6 Device construction 8 7 Programming 9 7 1 Select operation mode 9 7 2 Menu structure 9 7 3 Menues of operating modes 10 7 4 Characteristic curve te...

Page 3: ...9 Enclosure 14 9 1 Technical data 14 9 2 Connection diagram 15 9 3 Dimensions mm 16 9 4 Manufacturer reference 17 Operating Instructions TCA 150D L BAL E119 GB 1318 Index 002 Part No 00163357 GB 3 17 ...

Page 4: ...rmation contained in data illustrations or drawings provided We accept no liability for damage caused by misuse incorrect use improper use or as a consequence of unauthorized repairs or modifications 1 4 Copyright These operating instructions contain copyright protected information The operating instructions may be neither completely nor partially photocopied reproduced translated or put on data me...

Page 5: ...ions and in case the device fails Substitute operation must be taken into consideration 3 Product overview 3 1 Operational area Temperature control for e g extraction systems warm air heaters air curtain installa tions liquid cooling chillers Controlled output 0 10 V e g for activating a speed controller for fans Fans with integrated controller and input 0 10 V can be activated directly 3 2 Functi...

Page 6: ...rom the wall Do not allow drilling chips screws and other foreign bodies to reach the device interior The device should be installed in a location where it will not be disturbed but at the same time can be easily accessed Any cable ducts openings not used must be sealed Care must be taken to avoid direct radiation from the sun The device is designed for vertical installation cable inlet down A hor...

Page 7: ...ction diagram 5 2 EMC compatible installation of control lines Pay attention to maintain sufficient distance from powerlines and motor wires to prevent interferences The control cable may not be longer than 30 m Screened control cables must be used when the cable length is longer than 20 m 5 3 Connection Voltage supply Connection Voltage supply at terminals Ub and GND Here it must be strictly obser...

Page 8: ...roceed with electrical connection and programming Subsequently close carefully Ub GND A GND P 05 05 2010 v_ctg_bedien vsd D 27 5 C Actual Value TF TF 1 2 D LC Display Moon symbol Adjustment for Setpoint 2 active Exceeding measuring range sensor in terruption sensor short circuit Ub GND Voltage supply A GND Output signal 0 10 V TF TF Connection temperature sensor KTY81 210 or PT1000 1 2 Voltage inp...

Page 9: ...ual Value Display after turning on the voltage supply Switch over between actual value display and INFO with the key shortcut for Escape ESC INFO Example for Mode 2 01 Factory setting INFO SETTING BASE SETUP P ESC P ESC P ESC 20 0 C Actual Value 20 C Setpoint 1 2 01 Mode 20 C Setpoint 1 15 C Setpoint 2 KTY81 210 Sensortype 0 0 V Uout 5 0 K Pband 0 0 K Offset 2058 Ω Resistor 0 0 V Min Uout OFF MSCO...

Page 10: ...er Set ting Function Mode 2 00 2 01 Mode INFO Actual Value 27 1 C 27 1 C Display actual temperature Setpoint 1 20 0 C Display active Setpoint Uout 5 0 V 5 0 V Magnitude of the output voltage 0 10 V Resistor 2049 Ω 2049 Ω current resistance value of the temperature sensor UNIcon 1 00 1 00 software version SETTING Setpoint 1 20 0 C Setpoint1 Setting range 50 0 150 0 C Factory setting 20 0 C Setpoint...

Page 11: ... V than no diconnection of the output takes place does not go under Min Uout MSCO 2 0 K example It takes place a disconnection from Setting Min Uout to 0 if the given difference is reached related to the Setpoint At a plus value before reaching the de sired value At a minus value after falling below the desired value Hysteresis H ON OFFs approx 1 K Setting range 10 0 K 10 0 K Value Set n ON Contro...

Page 12: ...ams temperature control Cooling Value Set n ON 20 C Setpoint 05 05 2010 v_temp_cool_ctg vsd 24 C Uout V 5 10 Actual Value C Min Uout 3 5 V Max Uout 8 5 V Min Uout 0 0 V Max Uout 10 0 V 4 K Pband Heating Value Set n OFF 20 C Setpoint 4 K Pband 05 05 2010 v_temp_heat_ctg vsd 16 C Max Uout 10 0 V Min Uout 0 0 V Max Uout 8 5 V Min Uout 3 5 V Uout V Actual Value C 10 5 Operating Instructions TCA 150D P...

Page 13: ... on the rating plate 4 Set the operating Mode in the BASE SETUP factory settings 2 01 5 When saving the Operating Mode the factory settings are stored Therefore the settings you have made e g in SETTING are lost Attention electrostatic sensitive devices Be sure to ground the board at a suitable point in order to prevent damage to the electronic components being caused by electrostatic discharges S...

Page 14: ...4 mA LC Display double row max 16 digits each Housing Cover ABS bottom Polyamid PA 6 6 Fire protection classification UL 94 HB Protection class IP54 according EN 60529 Weight approx 200 g Permissible ambient temperature 10 C 50 C Permissible rel humidity 85 no condensation Interference emission according EN 61000 6 3 domestic household applications Interference immunity according 61000 6 2 industri...

Page 15: ...ax 0 3 mA 2 10 24 V DC 4 Ri 4 kΩ 0 1 0 Setpoint 1 1 Setpoint 2 q TF TF TF KTY 81 210 PT 1000 3 1 Voltage supply 10 24 V DC 2 Output 0 10 V 3 Temperature sensor KTY 81 210 or PT 1000 4 Voltage input for switch over Setpoint 1 Setpoint 2 Operating Instructions TCA 150D Enclosure L BAL E119 GB 1318 Index 002 Part No 00163357 GB 15 17 ...

Page 16: ...9 3 Dimensions mm GM00009A 12 05 2010 104 70 95 4 5 114 108 56 Operating Instructions TCA 150D Enclosure L BAL E119 GB 1318 Index 002 Part No 00163357 GB 16 17 ...

Page 17: ... have any questions concerning the use of our products or plan special uses please contact Systemair Industrievägen 3 73930 Skinnskatteberg Telefon 46 0 222 440 00 Telefax 46 0 222 440 99 mailbox systemair se www systemair se Operating Instructions TCA 150D Enclosure L BAL E119 GB 1318 Index 002 Part No 00163357 GB 17 17 ...

Reviews: