Parameter
Factory setting
User Set-
ting
Function
BASE SETUP
Mode
2.00
2.01
Mode selection
Sensortype
KTY81-210
KTY81-210
Setting type of sensor: KTY81-210 or
PT1000
Range min. Tem-
perature
-50
°
C
-
Setting measuring range, minimum temper-
ature value
Setting range: -50...150
°
C
Factory setting: -50
°
C
Range max.
Temperature
150
°
C
-
Setting measuring range, maximum tem-
perature value
Setting range: 150...-50
°
C
Factory setting: 150
°
C
Offset
0.0 K
0.0 K
Sensor offset
MSCO
-
OFF
Minimum speed cut off
|
MSCO
|
:
|
OFF
|
(factory setting)
If
“
Min. Uout
”
is adjusted (e.g. 2.0 V), than
no diconnection of the output takes place
(does not go under
“
Min. Uout)
”
.
|
MSCO
|
:
|
-2.0 K
|
(example)
It takes place a disconnection from Setting
“
Min. Uout
”
to
“
0
”
, if the given difference is
reached related to the Setpoint.
At a plus value (+) before reaching the de-
sired value
At a minus value (-) after falling below the
desired value.
Hysteresis
|
H
|
ON /OFFs: approx. 1 K
Setting range: -10.0 K...+10.0 K
Value>Set = n+
-
ON
Controller function
|
Value>Set = n+
|
:
|
ON
|
Cooling = increas-
ing modulation for increasing actual value
over Setpoint.
|
Value>Set = n+
|
:
|
OFF
|
Heating = increas-
ing modulation for decreasing actual value
below Setpoint.
-
Parameter for selected mode not available