You can go to the menu items in the menu groups (e.g. mode) by using the
P
key. Use
the arrow keys to move up and down within the menu group.
To make adjustments, press the
P
key after selecting the menu item. If the previously set
value starts to
fl
ash, it can be adjusted with the
▼
+
▲
keys and then saved with the
P
key. To exit the menu without making any changes, use the
“
Esc
”
short-key, i.e., the
originally set values remain.
Reprogramming Mode
2.01
to
2.00
in
“
BASE SETUP
”
1
2
3
4
5
6
7
2.01
Mode
P
«
2.01
»
Mode
▲
«
2.00
»
Mode
P
2.00
Mode
7.3 Menues of operating modes
Parameter
Factory setting
User Set-
ting
Function
Mode
2.00
2.01
Mode
INFO
Actual Value
27.1
°
C
27.1
°
C
Display actual temperature
Setpoint 1
-
20.0
°
C
Display active Setpoint
Uout
5.0 V
5.0 V
Magnitude of the output voltage 0...10 V
Resistor
2049
Ω
2049
Ω
current resistance value of the temperature
sensor
UNIcon
1.00
1.00
software version
SETTING
Setpoint 1
-
20.0
°
C
Setpoint1
Setting range: -50.0...+150.0
°
C
Factory setting: 20.0
°
C
Setpoint 2
-
15.0
°
C
Setpoint 2 active, if voltage at terminals 1, 2
Setting range: -50.0...+150.0
°
C
Factory setting: 15.0
°
C
Pband
-
5.0 K
Pband
Setting range: 1.0...50.0 K
Factory setting: 5.0 K
Min. Uout
0.0 V
0.0 V
Setting minimal output voltage
Max. Uout
10.0 V
10.0 V
Setting maximal output voltage
Operating Instructions
TCA 150D
Programming
L-BAL-E119-GB 1318 Index 002
Part.-No. 00163357-GB
10/17